Download Print this page

Honeywell EXCEL 10 Installation Instructions Manual page 4

Fan coil unit controllers
Hide thumbs Also See for EXCEL 10:

Advertisement

EXCEL 10 W7754K,P,Q,R,S,T,V FCU CONTROLLERS − INSTALLATION INSTRUCTIONS
Power Supply
General Information
CAUTION
To prevent a risk of injury due to electrical shock
and/or damage to device due to short-circuiting, low-
voltage and high-voltage lines must be kept physically
separate from one another.
NOTE: All wiring must comply with applicable electrical
codes and ordinances. Refer to job or manu-
facturers' drawings for details. Local wiring guide-
lines (e.g., IEC 364-6-61 or VDE 0100) may take
precedence over recommendations provided in
these installation instructions.
NOTE: To comply with CE requirements, devices having a
voltage of 50...1000 Vac or 75...1500 Vdc but lacking
a supply cord, plug, or other means for disconnecting
from the power supply must have the means of
disconnection incorporated in the fixed wiring. This
means of disconnection must have a contact
separation of at least 3 mm at all poles.
Use a min. of 18 AWG (1.0 mm
(2.5 mm
2
) for all power wiring.
Power is supplied via a removable terminal plug (attached to
terminals 25, 26) allowing individual units to be disconnected
from the power supply without disturbing the operation of
other devices powered by the same source. See Fig. 5.
Excel 10
W7754K,P,R,S,T,V
230
230
Vac
Vac
25
26
230
230
Vac
Vac
25
26
230
230
Vac
Vac
25
26
N
L
230 Vac (-15% / +10%),
50 / 60 Hz
Fig. 5. Connection to power supply
NOTE: To prevent a risk of short-circuiting and damage to
your unit, do not reverse the polarity of the power
connection cables, and avoid ground loops (i.e.
avoid connecting one field device to several
controllers).
EN1B-0304GE51 R0916M
2
) and a max. of 14 AWG
Excel 10
W7754Q
24
24
Vac
Vac
25
26
24
24
Vac
Vac
25
26
24 Vac
(+/-20%)
N
L
230 Vac (-15% / +10%),
50 / 60 Hz
Electrical Data
230 Vac +10%, -15%, 50/60 Hz;
W7754K,P,R,S,V:
max. 6 VA power consumption (unloaded)
230 Vac +10%, -15%, 50/60 Hz;
W7754T:
max. 12 VA power consumption (unloaded)
24 Vac 20%, 50/60 Hz
W7754Q:
max. 6 VA power consumption (unloaded)
Wall Modules
The T7460 and T7560 Wall Modules can be used in con-
junction with the W7754 to perform room temperature
sensing, set-point adjustment, fan speed manual override,
and occupancy override. When hardwired to the controller (via
terminals 4, 5, 6, 9, and 10), the wall module's LED/LCD can
be configured to provide information about
any override of the controller by, e.g., manual operation of
the wall module or the receipt by the controller of a net-
work command (see section "Configuration of LED to
Display Info on Overrides" below);
the controller's effective occupancy mode (see sections
"Configuration of LED to Display Info on Occupancy
Mode" and "Configuration of LCD to Display Info on
Occupancy Mode" below).
NOTE: The left DIP switch located on the top of the con-
troller (see Fig. 1 on page 1) is used to indicate that
a wall module can be hardwired to the controller.
Setting the left DIP switch to USED means that a
wall module can be hardwired; setting it to UNUSED
means that no wall module can be hardwired. Use
only an appropriate tool (e.g., ball-point pen) to set
the DIP switch.
NOTE: The intended use of the wall module's buttons must
be configured using Honeywell's LNS plug-in.
Table 3. Supported wall module functions
T7560 button
T7460C
--
--
T7460D
T7460E
--
--
T7460F
left
T7560A
middle
right
left
middle
T7560B
right
Example:
The T7560A has a left button configurable as a fan speed
button, a middle button configurable as a unit ON/OFF button,
and a right button for override. See T7460 Wall Modules
Installation Instructions (95-7610) and T7560 Digital Wall
Module Installation Instructions (EN1B-0146GE51) for details.
4
override unit ON/OFF fan speed
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--

Advertisement

loading