Type code

The type code of the drive is indicated on the type designation label, attached on the
cabinet door. The type code contains information on the specifications and
configuration of the drive. The first digits from left express the basic configuration
(e.g. ACS800-37-0490-3). The optional selections are given thereafter, separated by
+ signs (e.g. +E202). The main selections are described below.
Note: The information below is for quick reference only and does not contain all
conditions and details. For more information, refer to ACS800 Ordering Information
(code: 64556568), available through ABB representatives.

Frame sizes R6, R7i and R8i

Selection
Product series
Type
Size
Voltage range
(nominal rating in bold)
+ options
Supply frequency
I/O options
Fieldbus adapter
Application program
Degree of protection
Construction
Resistor braking
Filters
Alternatives
ACS800 product series
37 = cabinet-mounted
Default configuration: IP21 (UL Type 1); main switch/disconnector with aR-
type AC fuses; 50 Hz supply; 230 V AC auxiliary voltage; RDCO-03 DDCS
Communication Option; CDP-312R Control Panel; EMC/RFI filtering for 2nd
Environment (+E200) (except frame R6); common mode filtering; Standard
Application Program; bottom entry/exit of cables; coated circuit boards; set of
English manuals.
Refer to
Technical
data:
IEC
3 = 380/400/415 V AC
5 = 380/400/415/440/460/480/500 V AC
7 = 525/575/600/690 V AC
A013 = 60 Hz
Refer to ACS800 Ordering Information (code: 64556568 [English]).
B053 = IP22 (UL Type 1)
B054 = IP42 (UL Type 1)
B055 = IP54 (UL Type 12) – Not available with +C134
B059 = IP54R with connection to air outlet duct
C121 = Marine construction (reinforced mechanical parts and fastening,
marking of conductors [A1], door handles, self-extinctive materials)
C129 = UL Listed – Includes +H358
C134 = CSA Approved – Includes +H358
D150 = Brake chopper(s).
D151 = Brake resistors. Not available in IP54 or IP54R. Not available with
+C129 or +C134.
E200 = EMC/RFI filtering for 2nd Environment (frame R6 only; standard with
frame R7i and R8i)
E202 = EMC/RFI filtering for 1st Environment TN (grounded) system,
restricted (A-limits). Only available for certain types. Not available for 690 V.
E205 = du/dt filtering
E206 = Sine filter – Not available with +C121 or +C129.
ratings.