Fixed Parameters With The Acs800-37 - ABB ACS800-37-0060-3 Hardware Manual

Acs800-37 series drives (55 to 2700 kw / 75 to 3000 hp)
Table of Contents

Advertisement

No.
Name/Value
31.02
TRIAL TIME
1.0 ... 180.0 s
31.03
DELAY TIME
0.0 ... 3.0 s
31.04
OVERCURRENT
NO
YES
31.05
OVERVOLTAGE
NO
YES
31.06
UNDERVOLTAGE
NO
YES

Fixed parameters with the ACS800-37

When the IGBT Supply Control Program is loaded into the ACS800-37, the following
parameters receive the default values given in the table below.
Parameter
11.01
11.02
98.01
98.02
201.09
202.01
30.02
70.01
70.19
70.20
71.01
Description
Defines the time for the automatic fault reset function. See parameter
31.01.
Allowed resetting time
Defines the time that the drive will wait after a fault before attempting
an automatic reset. See parameter 31.01.
Resetting delay
Activates/deactivates the automatic reset for the line converter
overcurrent fault.
Inactive
Active
Activates/deactivates the automatic reset for the intermediate link
overvoltage fault.
Inactive
Active
Activates/deactivates the automatic reset for the intermediate link
undervoltage fault.
Inactive
Active
DC REF SELECT
Q REF SELECT
COMMAND SEL
COMM. MODULE
PANEL DRIVE ID
LOCAL LOCK
EARTH FAULT
CH0 NODE ADDR
CH0 HW CONNECTION RING
CH3 HW CONNECTION RING
CH0 DRIVEBUS MODE NO
Default value
FIELDBUS
PARAM 24.02
MCW. Note: If par. 16.15 I/O
START MODE is set to DI2 LEVEL,
the default value is changed to I/O
on the next RMIO board power-up.
INVERTER
2
TRUE
FAULT
120
T./FbEq
R
100 ...
18000
R
0 ... 300
B
0
65535
B
0
65535
B
0
65535
If changed,
the default values will be
restored on the next power-
up
the default values will not
be restored on the next
power-up. Do not change
them. If the default values
are changed, the drive will
not function.
Installation checklist and start-up
105
Def.
30 s
0 s
NO
NO
NO