Modbus User Map - GE L60 Instruction Manual

Line phase comparison relay, ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

5 SETTINGS
If SNTP functionality is enabled at the same time as IRIG-B, the IRIG-B signal provides the time value to the L60 clock for
as long as a valid signal is present. If the IRIG-B signal is removed, the time obtained from the SNTP server is used. If
either SNTP or IRIG-B is enabled, the L60 clock value cannot be changed using the front panel keypad.
To use SNTP in unicast mode,
set and
is "Enabled", the L60 attempts to obtain time values from the SNTP/NTP server. Since many time
SNTP FUNCTION
values are obtained and averaged, it generally takes three to four minutes until the L60 clock is closely synchronized with
the SNTP/NTP server. It may take up to two minutes for the L60 to signal an SNTP self-test error if the server is offline.
To use SNTP in broadcast mode, set the
L60 then listens to SNTP messages sent to the "all ones" broadcast address for the subnet. The L60 waits up to eighteen
minutes (>1024 seconds) without receiving an SNTP broadcast message before signaling an SNTP self-test error.
The UR-series relays do not support the multicast or anycast SNTP functionality.
PATH: SETTINGS
PRODUCT SETUP

MODBUS USER MAP

MESSAGE
MESSAGE
The Modbus User Map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desired
address in the
line (this value must be converted from hex to decimal format). The corresponding value is dis-
ADDRESS
played in the
line. A value of "0" in subsequent register
VALUE
lines incremented by "1". An address value of "0" in the initial register means "none" and values of "0" will be dis-
ADDRESS
played for all registers. Different
GE Multilin
must be set to the SNTP/NTP server IP address. Once this address is
SNTP SERVER IP ADDR
SNTP SERVER IP ADDR
MODBUS USER MAP
ADDRESS
1:
VALUE:
0
ADDRESS
2:
VALUE:
0
ADDRESS 256:
VALUE:
0
values can be entered as required in any of the register positions.
ADDRESS
L60 Line Phase Comparison Relay
setting to "0.0.0.0" and
SNTP FUNCTION
Range: 0 to 65535 in steps of 1
0
Range: 0 to 65535 in steps of 1
0
Range: 0 to 65535 in steps of 1
0
lines automatically returns values for the previous
ADDRESS
5.2 PRODUCT SETUP
to "Enabled". The
5.2.5 MODBUS USER MAP
5-27