B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 36 of 64)
ADDR
REGISTER NAME
7B6B
User Programmable Pushbutton 1 On Text
7B75
User Programmable Pushbutton 1 Off Text
7B7F
User Programmable Pushbutton 1 Drop-Out Time
7B80
User Programmable Pushbutton 1 Target
7B81
User Programmable Pushbutton 1 Events
B
7B82
User Programmable Pushbutton 1 LED Operand
7B83
User Programmable Pushbutton 1 Autoreset Delay
7B84
User Programmable Pushbutton 1 Autoreset Function
7B85
User Programmable Pushbutton 1 Local Lock Operand
7B86
User Programmable Pushbutton 1 Message Priority
7B87
User Programmable Pushbutton 1 Remote Lock Operand
7B88
User Programmable Pushbutton 1 Reset Operand
7B89
User Programmable Pushbutton 1 Set Operand
7B8A
User Programmable Pushbutton 1 Hold
7B8B
...Repeated for User Programmable Pushbutton 2
7BB6
...Repeated for User Programmable Pushbutton 3
7BE1
...Repeated for User Programmable Pushbutton 4
7C0C
...Repeated for User Programmable Pushbutton 5
7C37
...Repeated for User Programmable Pushbutton 6
7C62
...Repeated for User Programmable Pushbutton 7
7C8D
...Repeated for User Programmable Pushbutton 8
7CB8
...Repeated for User Programmable Pushbutton 9
7CE3
...Repeated for User Programmable Pushbutton 10
7D0E
...Repeated for User Programmable Pushbutton 11
7D39
...Repeated for User Programmable Pushbutton 12
7D64
...Repeated for User Programmable Pushbutton 13
7D8F
...Repeated for User Programmable Pushbutton 14
7DBA
...Repeated for User Programmable Pushbutton 15
7DE5
...Repeated for User Programmable Pushbutton 16
Underfrequency (Read/Write Setting) (6 modules)
7E10
Underfrequency Function
7E11
Underfrequency 1 Block
7E12
Underfrequency 1 Minimum Current
7E13
Underfrequency 1 Pickup
7E14
Underfrequency 1 Pickup Delay
7E15
Underfrequency 1 Reset Delay
7E16
Underfrequency 1 Source
7E17
Underfrequency 1 Events
7E18
Underfrequency 1 Target
7E19
Underfrequency 1 Reserved (8 items)
7E21
...Repeated for Underfrequency 2
7E32
...Repeated for Underfrequency 3
7E43
...Repeated for Underfrequency 4
7E54
...Repeated for Underfrequency 5
7E65
...Repeated for Underfrequency 6
Neutral Overvoltage (Read/Write Grouped Setting) (3 modules)
7F00
Neutral Overvoltage 1 Function
7F01
Neutral Overvoltage 1 Signal Source
7F02
Neutral Overvoltage 1 Pickup
7F03
Neutral Overvoltage 1 Pickup Delay
7F04
Neutral Overvoltage 1 Reset Delay
7F05
Neutral Overvoltage 1 Block
7F06
Neutral Overvoltage 1 Target
7F07
Neutral Overvoltage 1 Events
B-44
RANGE
---
---
0 to 60
0 to 2
0 to 1
0 to 65535
0.2 to 600
0 to 1
0 to 65535
0 to 2
0 to 65535
0 to 65535
0 to 65535
0 to 10
0 to 1
0 to 65535
0.1 to 1.25
20 to 65
0 to 65.535
0 to 65.535
0 to 5
0 to 1
0 to 2
0 to 1
0 to 1
0 to 5
0 to 3
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
F60 Feeder Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
---
F202
---
---
F202
s
0.05
F001
---
1
F109
---
1
F102
---
1
F300
s
0.1
F001
---
1
F102
---
1
F300
---
1
F220
---
1
F300
---
1
F300
---
1
F300
s
0.1
F001
---
1
F102
---
1
F300
pu
0.01
F001
Hz
0.01
F001
s
0.001
F001
s
0.001
F001
---
1
F167
---
1
F102
---
1
F109
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
DEFAULT
(none)
(none)
0
0 (Self-reset)
0 (Disabled)
0
10
0 (Disabled)
0
0 (Disabled)
0
0
0
1
0 (Disabled)
0
10
5950
2000
2000
0 (SRC 1)
0 (Disabled)
0 (Self-reset)
0
0 (Disabled)
0 (SRC 1)
300
100
100
0
0 (Self-reset)
0 (Disabled)
GE Multilin