ABB REQ650 Product Manual page 40

Relion 650 series breaker protection 2.1 iec
Hide thumbs Also See for REQ650:
Table of Contents

Advertisement

Breaker protection REQ650 2.1 IEC
Product version: 2.1
Table 31. General current and voltage protection CVGAPC , continued
Function
Independent time delay, undervoltage at 1.2 to 0.8 x U
- 2
Overvoltage:
Start time at 0.8 to 1.2 x U
set
Reset time at 1.2 to 0.8 x U
set
Undervoltage:
Start time at 1.2 to 0.8 x U
set
Reset time at 1.2 to 0.8 x U
set
Overvoltage:
Inverse time characteristics, see table
Undervoltage:
Inverse time characteristics, see table
High and low voltage limit, voltage dependent operation, step 1 -
2
Directional function
Relay characteristic angle
Relay operate angle
Reset ratio, overcurrent
Reset ratio, undercurrent
Reset ratio, overvoltage
Reset ratio, undervoltage
Overcurrent:
Critical impulse time
Impulse margin time
Undercurrent:
Critical impulse time
Impulse margin time
Overvoltage:
Critical impulse time
Impulse margin time
Undervoltage:
Critical impulse time
Impulse margin time
40
Range or value
, step 1
(0.00 - 6000.00) s
set
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
""
4 curve types
106
3 curve types
(1.0 - 200.0)% of UBase
Settable: NonDir, forward and reverse
(-180 to +180) degrees
(1 to 90) degrees
> 95%
< 105%
> 95%
< 105%
10 ms typically at 0 to 2 x I
15 ms typically
10 ms typically at 2 to 0 x I
15 ms typically
10 ms typically at 0.8 to 1.2 x U
15 ms typically
10 ms typically at 1.2 to 0.8 x U
15 ms typically
1MRK 505 358-BEN B
Accuracy
±0.2% or ±35 ms whichever is
greater
-
-
-
-
See table
""
See table
106
±1.0% of U
r
±1.0% of U at U > U
-
±2.0 degrees
±2.0 degrees
-
-
-
-
-
set
-
-
set
-
-
set
-
-
set
-
at U ≤ U
r
r
ABB