  • Page 1 ® Relion 650 series Breaker protection REQ650 2.1 IEC Product guide...
  • Page 2: Table Of Contents

    Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. Drawings and diagrams are not binding.
  • Page 3: Application

    REQ650 provides an optimized standalone product. access control to IEDs and other systems within a substation. REQ650 provides backup to the main protection with This incorporates management of user accounts, roles and redundant protection and control functions.
  • Page 4 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 REQ650 B11 – Single breaker with single phase tripping 12AI (7I+5U) WA2_VT VN MMXU WA1_VT 1->0 1→0 SC/VC 5(0→1) VN MMXU SMP PTRC SMP PTRC SMB RREC SES RSYN...
  • Page 5: Available Functions

    1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 2. Available functions Back-up protection functions GUID-A8D0852F-807F-4442-8730-E44808E194F0 v11 IEC 61850 ANSI Function description Breaker REQ650 (B11) Current protection PHPIOC Instantaneous phase overcurrent protection OC4PTOC Four step phase overcurrent protection...
  • Page 6: Secondary System Supervision

    1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Control and monitoring functions GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v13 IEC 61850 ANSI Function description Breaker REQ650 (B11) Control SESRSYN Synchrocheck, energizing check and synchronizing SMBRREC Autorecloser QCBAY Apparatus control LOCREM Handling of LRswitch positions...
  • Page 7: Monitoring

    1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 IEC 61850 ANSI Function description Breaker REQ650 (B11) TEIGAPC Elapsed time integrator with limit transgression and overflow supervision INTCOMP Comparator for integer inputs REALCOMP Comparator for real inputs...
  • Page 8 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Table 1. Total number of instances for basic configurable logic blocks Basic configurable logic block Total number of instances GATE PULSETIMER RSMEMORY SRMEMORY TIMERSET...
  • Page 9 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Communication GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v13 IEC 61850 ANSI Function description Breaker REQ650 (B11) Station communication LONSPA, SPA SPA communication protocol LON communciation protocol HORZCOMM Network variables via LON PROTOCOL Operation selection between SPA and IEC 60870-5-103 for SLM...
  • Page 10 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 IEC 61850 ANSI Function description Breaker REQ650 (B11) FSTACCS, Field service tool access via SPA protocol over ethernet communication FSTACCSNA ACTIVLOG Activity logging parameters ALTRK Service Tracking SINGLELCCH...
  • Page 11 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Basic IED functions GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v10 Table 2. Basic IED functions IEC 61850 or function Description name INTERRSIG Self supervision with internal event list SELFSUPEVLST Self supervision with internal event list...
  • Page 12 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Table 3. Local HMI functions IEC 61850 or function ANSI Description name LHMICTRL Local HMI signals LANGUAGE Local human machine language SCREEN Local HMI Local human machine screen behavior FNKEYTY1–FNKEYTY5...
  • Page 13 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 An alarm level gives early warning to allow operators to take Two step overvoltage protection OV2PTOV action well before the line is tripped. M13798-3 v14 Overvoltages may occur in the power system during abnormal...
  • Page 14 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 with the neutral point current on a separate input taken from difference, phase angle difference, slip frequency and another set of cores on the current transformer. frequency rate of change before issuing a controlled closing of the circuit breaker.
  • Page 15 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 GUID-D8D1A4EE-A87F-46C6-8529-277FC1ADA9B0 v3 Selector mini switch VSGAPC The group indication logic function INDCALH is used to route SEMOD158756-5 v8 The Selector mini switch VSGAPC function block is a several indication signals to a common indication, LED and/or multipurpose function used for a variety of applications, as a contact, in the IED.
  • Page 16 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 a certain level/value, or for creating certain logic. Boolean, GUID-A93564FA-0017-4939-A9C1-095DA0FD9832 v1 The function gives the possibility to monitor the level of integer, floating point, string types of signals are available.
  • Page 17 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 to all events, which are continuously saved in a -buffer. The The trip value recorder information is an integrated part of the local HMI is used to get information about the recordings. The disturbance record (Comtrade file).
  • Page 18: Human Machine Interface

    1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 tEnergy . The integration of active and reactive energy time Event counter with limit supervison L4UFCNT values will happen in both forward and reverse directions. GUID-13157EAB-1686-4D2E-85DF-EC89768F3572 v5 The 30 limit counter L4UFCNT provides a settable counter...
  • Page 19: Basic Ied Functions

    SEMOD120134-5 v1 A single glass or plastic port is provided for the ABB SPA The two high speed signal output channels are used for protocol. This allows extensions of simple substation applications where short operating time is essential.
  • Page 20 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 M2152-3 v5 Optical ethernet module OEM M16073-3 v6 The optical fast-ethernet module is used for fast and interference-free communication of synchrophasor data over IEEE C37.118 and/or IEEE 1344 protocols. It is also used to connect an IED to the communication buses (like the station bus) that use the IEC 61850-8-1 protocol (port A, B).
  • Page 21 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 See ordering for details about available mounting alternatives.
  • Page 22: Connection Diagrams

    1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 15. Connection diagrams The latest versions of the connection diagrams can be downloaded from http://www.abb.com/substationautomation. Connection diagrams GUID-CF4EFFA5-3081-4FC7-9A14-ED127C3C0FDE v4 The connection diagrams are delivered on the IED 650 series ver. 2.1, IEC symbols 1MRK006501-AF Connectivity package DVD as part of the product delivery.
  • Page 23: Technical Data

    1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 16. Technical data General M10993-1 v3 IP11376-1 v2 Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range...
  • Page 24 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Analog inputs M16988-1 v10 IP15842-1 v1 Table 4. TRM - Energizing quantities, rated values and limits for protection transformer modules Quantity Rated value Nominal range Current = 1 or 5 A (0.2-40) ×...
  • Page 25 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Table 7. BIM - Binary input module with enhanced pulse counting capabilities Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20%...
  • Page 26 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Influencing factors M16705-1 v10 IP15846-1 v1 Table 9. Temperature and humidity influence Parameter Reference value Nominal range Influence Ambient temperature, operate +20°C -20°C to +55°C 0.02%/°C value Relative humidity...
  • Page 27 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Table 12. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV...
  • Page 28 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Table 14. Environmental tests Test Type test value Reference standard Cold operation test Test Ad for 16 h at -25°C IEC 60068-2-1 Cold storage test Test Ab for 16 h at -40°C...
  • Page 29 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Current protection M12336-1 v12 Table 17. PHPIOC Function Range or value Accuracy Operate current (5-2500)(5–1200)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 30 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 M12342-1 v18 Table 18. Four-step phase overcurrent protection OC4PTOC Function Setting range Accuracy Operate current, step 1-4 (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I > I...
  • Page 31 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 M15223-1 v16 Table 20. Four step residual overcurrent protection EF4PTOC technical data Function Range or value Accuracy Operate current, step 1-4 (1-2500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 32 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v5 Table 21. Four step negative sequence overcurrent protection NS4PTOC Function Range or value Accuracy Operate current, step 1 - 4 (1-2500)% of lBase ±1.0% of I at I £...
  • Page 33 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 M12352-1 v13 Table 22. Thermal overload protection, one time constant LCPTTR/LFPTTR Function Range or value Accuracy Reference current (2-400)% of IBase ±1.0% of I Reference temperature (0-300)°C, (0 - 600)°F ±1.0°C, ±2.0°F...
  • Page 34 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 M12350-1 v11 Table 24. Stub protection STBPTOC Function Range or value Accuracy Operating current (5-2500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I...
  • Page 35 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Voltage protection M13290-1 v14 Table 26. Two step undervoltage protection UV2PTUV Function Range or value Accuracy UBase Operate voltage, low and high step (1.0–100.0)% of ±0.5% of U Absolute hysteresis (0.0–50.0)% of...
  • Page 36 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 M13304-1 v13 Table 27. Two step overvoltage protection OV2PTOV Function Range or value Accuracy Operate voltage, step 1 and 2 (1.0-200.0)% of UBase ±0.5% of U at U ≤ U ±0.5% of U at U >...
  • Page 37 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Table 29. Two step residual overvoltage protection ROV2PTOV Function Range or value Accuracy Operate voltage, step 1 - step 2 (1.0-200.0)% of UBase ± 0.5% of U at U ≤ U ±...
  • Page 38 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Multipurpose protection M13095-2 v7...
  • Page 39 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Table 31. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, - NegSeq, -3*ZeroSeq, MaxPh, MinPh, UnbalancePh, phase1-phase2, phase2-...
  • Page 40 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Table 31. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Independent time delay, undervoltage at 1.2 to 0.8 x U , step 1 (0.00 - 6000.00) s...
  • Page 41 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 SEMOD175176-2 v5 Table 32. Rotor earth fault protection Function Range or value For machines with: • rated field voltage up to 350 V DC • static exciter with rated supply...
  • Page 42: Fuse Failure Supervision

    1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Secondary system supervision M12358-1 v8 Table 33. Current circuit supervision CCSSPVC Function Range or value Accuracy Operate current (10-200)% of IBase ±10.0% of I at I ≤ I ±10.0% of I at I >...
  • Page 43 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Control M12359-1 v13 Table 36. Synchronizing, synchrocheck and energizing check SESRSYN Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase...
  • Page 44 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Table 37. Synchronizing, synchrocheck and energizing check SESRSYN Function Range or value Accuracy (-180 to 180) degrees Phase shift, j line Voltage high limit for synchronizing and synchrocheck (10.0-120.0)% of Ubase...
  • Page 45 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 M12379-1 v12 Table 38. Autorecloser SMBRREC Function Range or value Accuracy Number of autoreclosing shots Autoreclosing open time: shot 1 - t1 1Ph (0.000-120.000) s ±0.2% or ±35 ms...
  • Page 46 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Table 39. Autorecloser SMBRREC Function Range or value Accuracy Number of autoreclosing shots Autoreclosing open time: shot1 - t1_HS, high speed reclosing without (0.000-20.000) s ±0.2% or ±20 ms whichever is greater...
  • Page 47 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Logic M12380-1 v10 Table 40. Tripping logic common 3-phase output SMPPTRC Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater 3-pole trip delay (0.020-0.500) s...
  • Page 48 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v1 Table 47. Number of INDCALH instances Function Quantity with cycle time 3 ms 8 ms 100 ms INDCALH GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v1 Table 48. Number of AND instances...
  • Page 49: Elapsed Time Integrator With Limit Transgression And Overflow Supervision

    1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 GUID-C6C98FE0-F559-45EE-B853-464516775417 v1 Table 55. Number of TIMERSET instances Logic block Quantity with cycle time Range or Value Accuracy 3 ms 8 ms 100 ms TIMERSET (0.000–90000.000) s ±0.5% ±10 ms GUID-0B07F78C-10BD-4070-AFF0-6EE36454AA03 v1 Table 56.
  • Page 50 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Table 62. Number of TEIGAPC instances Function Quantity with cycle time 3 ms 8 ms 100 ms TEIGAPC GUID-F5E124E3-0B85-41AC-9830-A2362FD289F2 v1 Table 63. Running hour-meter TEILGAPC Function Range or value...
  • Page 51: Measurements

    1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Monitoring M12386-1 v14 Table 64. Measurements CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) x f ±2.0 mHz Current (0.1-4.0) x I ±0.8% of I at 0.1 x I <...
  • Page 52: Measurements

    1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Table 69. Phase-phase voltage measurement VMMXU Function Range or value Accuracy Voltage magnitude (10 to 130) V ±0.5% of U Phase angle (10 to 130) V ±1.0 degrees at 10 V ≤ U ≤ 110 V ±2.0 degrees at 110 V <...
  • Page 53: Disturbance Report

    1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 GUID-47094054-A828-459B-BE6A-D7FA1B317DA7 v5 Table 74. Voltage sequence measurement VMSQI Function Range or value Accuracy Voltage positive sequence, U1 (10 to 300) V ±0.5% of U at U ≤ 50 V ±0.2% of U at U >...
  • Page 54 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 GUID-F034B396-6600-49EF-B0A5-8ED96766A6A0 v6 Table 78. Insulation gas monitoring function SSIMG Function Range or value Accuracy Pressure alarm level 1.00-100.00 ±10.0% of set value Pressure lockout level 1.00-100.00 ±10.0% of set value Temperature alarm level -40.00-200.00...
  • Page 55 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Table 81. Breaker monitoring SSCBR Function Range or value Accuracy Alarm level for open and close travel time (0 – 200) ms ±3 ms Alarm level for number of operations (0 –...
  • Page 56 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 M12384-1 v6.1.1 Table 86. Disturbance recorder Function Value Buffer capacity Maximum number of analog inputs Maximum number of binary inputs Maximum number of disturbance reports Maximum total recording time (3.4 s recording time and maximum number...
  • Page 57: Pulse-Counter Logic

    1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Metering M13404-2 v5 Table 88. Pulse-counter logic PCFCNT Function Setting range Accuracy Cycle time for report of counter (1–3600) s value SEMOD153707-2 v4 Table 89. ETPMMTR Function Range or value...
  • Page 58 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Station communication M15031-1 v7 M11927-1 v2 Table 90. LON communication protocol Function Value Protocol Communication speed 1.25 Mbit/s M11901-1 v2 Table 91. SPA communication protocol Function Value Protocol...
  • Page 59 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 GUID-8651FF22-C007-4D53-B7E3-686A30F37CB6 v4 Table 96. IEC 62439-3 Edition 1 and Edition 2 parallel redundancy protocol Function Value Communication speed 100 Base-FX...
  • Page 60 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Hardware M12327-1 v3 SEMOD53385-1 v1 Table 97. Water and dust protection level according to IEC 60529 Front IP40 (IP54 with sealing strip) Sides, top and bottom IP20 Rear side...
  • Page 61 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Basic IED functions M11963-1 v5 Table 101. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out SEMOD141136-2 v8 Table 102.
  • Page 62 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Inverse characteristic M12388-1 v19 Table 103. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 3.00 ANSI/IEEE C37.112 , 1.5 x I ≤...
  • Page 63 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Table 104. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 3.00 IEC 60255-151, ±2.0% 1.5 x I ≤ I ≤ 20 x I or ±40 ms whichever is...
  • Page 64 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 SEMOD116978-2 v9 Table 106. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 65: Ordering For Pre-Configured Ied

    To obtain the complete ordering code, please combine code from the tables, as given in the example below. Example code: REQ650*2.1-B11X00- P03-B1A12-AC-MP-B-A3X0-D1AB1N1-GXFX-AX. Using the code of each position #1-13 specified as REQ650*1-2 2-3-4 4-5-6-7 8-9-10 10 10 10-11 11 11-12 12 12 12-13 13...
  • Page 66 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Connection type Notes and Rules Connection type for Power supply module Compression terminals Ringlug terminals Connection type for input/output modules Compression terminals Selection for position #7. Auxiliary power supply...
  • Page 67 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Remote end communication, DNP serial comm. and time synchronization Notes and Rules modules Slot position (rear view) Available slots █ █ █ █ No remote communication board included...
  • Page 68: Ordering For Accessories

    1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 18. Ordering for Accessories RK926 315-AV is provided with one three-phase CT input with current shorting and with sixteen trip output blocking Accessories contacts. It is suitable when external CT grounding is required...
  • Page 69 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Rule: Specify additional quantity of IED Connect CD requested . Quantity: 1MRK 002 290-AD User documentation Rule: Specify the number of printed manuals requested Application manual Quantity: 1MRK 505 355-UEN...
  • Page 70 1MRK 505 358-BEN B Breaker protection REQ650 2.1 IEC Product version: 2.1 Reference information M2175-3 v4 For our reference and statistics we would be pleased to be provided with the following application data: Country: End user: Station name: Voltage level:...
  • Page 72 Contact us For more information please contact: Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. ABB AB ABB AB does not accept any responsibility whatsoever for potential Substation Automation Products errors or possible lack of information in this document.