Download Print this page

Jumper Settings - Honeywell T7460A Installation Instructions Manual

Excel 5000 open system wall modules

Advertisement

signal
T7460A
T7460B
terminal
terminal
sensor signal
1
COM/GND
3
SETPT
--
BYP/FAN
--
(no fan)
BYP/RTN
--
LED
(10Vdc/3mA
--
permanent)
LED/RTN
(0Vdc = LED OFF,
--
10Vdc = LED ON)
signal
T7460D
T7460D,E,F
terminal
terminal
sensor signal
2
COM/GND
1
SETPT
3
BYP/FAN
4
(no fan)
BYP/RTN
6
LED
(10Vdc/3mA
--
permanent)
LED/RTN
(0Vdc = LED OFF,
--
10Vdc = LED ON)
NOTE: In the case of Excel 10/12 wiring, please refer to the respective Excel 10/12 Installation Instructions.

Jumper Settings

See also Fig. 8. The jumpers on the PCB of the T7460C,D,E,F must be set according to the type of controller connected.
Jumper Setting 1 for W77xx
Const. Vol. Air Handling Unit
(Smart) Variable Air Volume
Fan Coil Unit (FCU2)
Fan Coil Unit (FCU3)
Remote Input/Output Device
Hydronic
Chilled Ceiling
Excel 12
Jumper Setting 2 for W7753
Unit Ventilator
Jumper Setting 3 for XL500
Excel 800
Excel 500
Excel 100
Excel 50
Excel 20
CPO-FCU
Smart I/O
T7460A,B,C,D,E,F WALL MODULES – INSTALLATION INSTRUCTIONS
Table 2. Wiring terminal references for non-Excel 10/12 devices
T7460C
Excel 800
terminal
XF82x
terminal
(example)
1
2
XF821: 1 (AI)
XF821: 11
3
1
(AI GND)
2
3
XF821: 2 (AI)
--
4
XF823: 1 (DI)
XF823: 13
--
6
(DI GND)
--
5
XF822: 1 (AO)
--
7
XF822: 2 (AO)
Excel 800
Excel 500
XF82x terminal
XF52xB terminal
(example)
(example)
2
XF821: 1 (AI)
XF521: 1 (AI)
XF821: 11
XF521: 2
1
(AI GND)
(AI GND)
3
XF821: 2 (AI)
XF521: 3 (AI)
4
XF821: 3 (AI)
XF521: 5 (AI)
XF821: 13
XF521: 6
6
(AI GND)
(AI GND)
5
XF822: 1 (AO)
XF522: 1 (AO)
7
XF822: 2 (AO)
XF522: 3 (AO)
W7750A,B
W7751B,D,F,H
W7752D,E,F,G
W7754
W7761A
W7762A,B
W7763C,D,E
W7704xx
W7753
XCL8010A
XC5010x, XC5210x
XL100x
XL50xxxx
XL20x
CPO-FB22344R-xxx
XFC2xxxx/XFC3xxxx
Excel 500
Excel 500
Excel 100
XF52xB
XFL52x
terminal
terminal
terminal
(example)
(example)
(example)
XF521: 1 (AI)
XFL521: 1 (AI)
XF521: 2
XFL521: 18
55 (GND)
(AI GND)
(AI GND)
XF521: 3 (AI)
XFL521: 2 (AI)
XF523: 1 (DI)
XFL523: 1 (DI)
XF523: 14
XFL523: 18
56 (GND)
(DI GND)
(DI GND)
XF522: 1 (AO)
XFL522: 1 (AO)
XF522: 3 (AO)
XFL522: 2 (AO)
Excel 500
Excel 100
XFL52x terminal
terminal
(example)
(example)
XFL521: 1 (AI)
1 (AI)
XFL521: 18
55 (GND)
(AI GND)
XFL521: 2 (AI)
2 (AI)
XFL521: 3 (AI)
3 (AI)
XFL521: 20
56 (GND)
(AI GND)
XFL522: 1 (AO)
37 (AO)
XFL522: 2 (AO)
38 (AO)
3
Excel 50
Excel 20
terminal
terminal
(example)
(example)
1 (AI)
33 (AI)
19 (AI)
34 (AI GND)
20 (AI GND)
2 (AI)
35 (AI)
21 (AI)
13 (DI)
23 (DI)
34 (DI)
24 (DI GND)
18 (COM)
37 (AO)
15 (AO)
12 (AO)
38 (AO)
17 (AO)
13 (AO)
Excel 50
Excel 20
terminal
terminal
(example)
(example)
33 (AI)
34 (AI GND)
20 (AI GND)
35 (AI)
37 (AI)
38 (AI GND)
24 (AI GND)
15 (AO)
12 (AO)
17 (AO)
13 (AO)
EN1B-0291GE51 R1111B
CPO-
Smart I/O
FB22344R
XFC2 / XFC3
terminal
terminal
(example)
(example)
39 (AI)
11 (AI)
40 (AI GND)
10 (AI GND)
41 (AI)
14 (AI)
36 (DI)
6 (DI)
37 (DI GND)
5 (DI)
19 (AO)
32 (AO)
17 (AO)
35 (AO)
CPO-FB22344R
terminal
(example)
19 (AI)
39 (AI)
40 (AI GND)
21 (AI)
41 (AI)
alternatively to
23 (AI)
SETPT
alternatively to
SETPT
19 (AO)
17 (AO)

Advertisement

loading

This manual is also suitable for:

T7460cT7460bT7460dT7460fT7460e