Base construction and installation of the DVM Hydro unit / Hydro unit HT

If this product is installed in residential area, apply anti-vibration product to prevent the vibration from
transferring to the building.
WARNING
Manufacturer is not responsible for the damage occurred by not following the installation standards.
1. Considering the vibration and weight of the DVM Hydro unit / Hydro unit HT, strength of the base ground must be strong
enough to prevent noise and the top part of the base ground has to be flat.
2. Base ground should be 1.5 times larger than the bottom of the Hydro unit.
3. It is necessary to add wire mesh or steel bar during concrete construction for the base ground to prevent damages or
cracks.
4. Place the DVM Hydro unit / Hydro unit HT on the base construction and completely fix it with the bolt, nut and washer.
(The bearing force has to be over 3.5 kN)
5. Fix the DVM Hydro unit / Hydro unit HT firmly with 4 foundation bolts.
6. When concrete construction for DVM Hydro unit / Hydro unit HT installation is completed, install an anti-vibration
pad(t=20 mm or more) or an anti-vibration frame(vibration transmissibility=5 % and below) to prevent vibration of the
outdoor unit from transferring to the base ground.
7. When constructing base ground, DVM Hydro unit / Hydro unit HT must be supported within the range of following
dimensions.
Base ground construction
Drain hole
200 mm or more
DVM Hydro unit installation
340
518
8
(Unit: mm)
Nut, Spring washer
DVM Hydro unit
Anchor bolt
20 mm
Anti-vibration pad
A
H beam or anti-vibration frame
A+10~20 mm or more