Table 2 - Conduit Adapters; Figure 9: Electronic Housing Conduit Entries - Honeywell ST 800 Quick Start Installation Manual

Standard smartline pressure transmitter
Hide thumbs Also See for ST 800:
Table of Contents

Advertisement

SmartLine Pressure Transmitter
Step
1
Remove the protective plastic cap from the threaded conduit entry.
To ensure the environmental ingress rating on tapered threads (NPT),
2
a non-hardening thread sealant may be used.
3
Thread the appropriate size adapter (M20 or ½ NPT) into the conduit
entry opening
4
Tighten adapters according to the following table.
½ to ¾ NPT Adapter

Figure 9: Electronic Housing Conduit Entries

Note. No plugs come installed in the housings. All housings come with temporary
plastic dust protectors (red) installed and are not certified for use in any installation
12

Table 2 - Conduit Adapters

Description
Quick Start Installation Guide
Action
Tool
1 ¼" Wrench
Torque
32Nm
24Lb-ft