GE Grid Solutions
Configuring the D25 to work with a DNP3 I/O Module
For example, when configuring your D25 RTU Master to work with a DNP
Example
Digital Input Module, assume that you have a DNP Digital Input Module:
Configuration
• That is factory-configured with 64 digital inputs
• That has DNP address 0032
• Which is to be polled every 500 ms.
• With every poll, we want a full status update.
To meet these requirements, you would configure the DNP DCA as shown in
the below table:
Remote Device Table
Remote Device Point
Mapping Table
Remote Device Polling Table
GE Information
Table
Application Address
DCA Object Type
Number of Device Points
Poll Data Type
Poll Interval
994-0081-3.00-21
, continued
Parameter
0032
Binary Input
64
Integrity
500 ms
D25
User's Manual
Value
79