Fujitsu AUYG07LVLA Design & Technical Manual page 272

Hide thumbs Also See for AUYG07LVLA:
Table of Contents

Advertisement

Limitation check
Total pipe length
Between outdoor unit and the farthest indoor unit
Between outdoor unit and branch box
Between branch box and indoor unit
Between outdoor unit and branch box
(When there is no separation tube)
Calculation of additional charge refrigerant
Liquid pipe size
mm (in.)
Additional refrigerant
g/m
Liquid pipe length
m
Additional charge = (21 x 39) + (58 x 45) = 3429 g = 3.43 kg
Diagram
Total
c + h
c
Total
f + g + h
Each unit
f, g, h
c
6.35
9.52
(1/4)
(3/8)
21
58
39
45
- (06 - 24) -
Example
Limitation
m
m
84
115 or less
60
70 or less
45
55 or less
39
60 or less
12 to 15
Between 3 to 15
45
5 or more
6. SYSTEM DESIGN
Judge
OK
OK
OK
OK
OK
OK