5 SETTINGS
To ensure element accuracy for high overcurrent conditions, the maximum value of I/(k x I
istically it is exceeding this value.
The reset time of the thermal overload protection element is also time delayed using following formula:
In the above equation,
τ
= thermal protection trip time constant
rst
T
is a minimum reset time setting
min
Figure 5–112: IEC 255-8 SAMPLE OPERATE AND RESET CURVES
The thermal overload protection element estimates accumulated thermal energy E using the following equations calculated
each power cycle. When current is greater than the pickup level, I
GE Multilin
(
kI
B
τ
×
---------------------------- -
t
ln
=
rst
rst
2
I
(
kI
E
E
=
+
n
n 1
C70 Capacitor Bank Protection and Control System
) is limited to 8, even when real-
B
2
)
T
+
min
2
)
B
> k × I
, element starts increasing the thermal energy:
n
B
t Δ
-------------- -
t
op In
(
)
5.7 CONTROL ELEMENTS
(EQ 5.23)
(EQ 5.24)