External Fault 2; External Fault 3 - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

10.3.3

"External fault 2"

Causes
Fault code F7861 ("External Fault 2") is triggered when the braking resistor available with
options L61 and L62 is subject to thermal overload, thereby activating the thermostat. The
drive is switched off with OFF2.
Remedy
The cause of the braking resistor overload must be eliminated and the fault code
acknowledged.
10.3.4

"External fault 3"

Causes
Fault code F7862 "External fault 3" is triggered when the braking unit fitted for options L61
and L62 triggers a fault. The drive is switched off with OFF2.
Remedy
The cause of the braking unit overload must be eliminated and the fault code acknowledged.
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Diagnosis / faults and alarms
10.3 Overview of warnings and faults
529

Advertisement

Table of Contents
loading

Table of Contents