Siemens SINAMICS G150 Operating Instructions Manual page 181

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

X482 Analog inputs/outputs
Table 4- 73
Terminal block X482
Terminal
1
2
3
4
5
6
7
8
Max. connectable cross-section: 0.5 mm
AI: analog input, AO: Analog output
1)
Note
An open input is interpreted as approximately "0 V".
The power supply of the analog inputs/outputs is drawn via the option slot of the Control Unit
and not via X424.
The shield is connected to the Control Unit.
CAUTION
The common-mode range must not be infringed.
The analog differential voltage signals can have a maximum offset voltage of +/-30 V with
respect to the ground potential. If the range is infringed, incorrect results may occur during
analog/digital conversion.
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Designation
1)
AI 0+
AI 0-
AI 1+
AI 1-
AO 0+
AO 0-
AO 1+
AO 1-
2
Technical data
Analog inputs (AI)
Voltage: -10 ... +10 V
internal resistance: 65 kΩ
Resolution: 13 bits + sign
Analog outputs (AO)
Voltage range: -10 ... +10 V
Load current: max. -3 ... +3 mA
Resolution: 11 bit + sign
Continuously short-circuit proof
Electrical installation
4.11 Other connections
179