Autoreclose Internal Status; 79 Internal Status - GE Multilin F650 Instruction Manual

Hide thumbs Also See for Multilin F650:
Table of Contents

Advertisement

5 SETPOINTS

5.5.5.4 AUTORECLOSE INTERNAL STATUS

Actual> Status > Control Elements >
relay; they are also useful to know the autoreclose behavior.
Table 5–77: 79 INTERNAL STATUS
AUTORECLOSE SINGLE STATUS
AR CLOSE BREAKER
AR OUT OF SERVICE
AR READY
AR LOCKOUT
AR BLOCK
AR RCL IN PROGRESS
AR LCK BY ANOMALY
AR LCK BY FAIL OPEN
AR LCK BY FAIL CLOSE
AR LCK BY USER
AR LCK BY CONDS
AR LCK BY TRIPS
AR LCK BY SHOTS
AR BLK AFTER 1 SHOT
AR BLK AFTER 2 SHOT
AR BLK AFTER 3 SHOT
AR BLK AFTER 4 SHOT
AR BLOCK BY LEVEL
AR BLOCK BY PULSE
Description of autoreclose internal status:
AR CLOSE BREAKER
Breaker close command given by the autoreclose
AR OUT OF SERVICE
Autoreclose out of service (Disabled)
AR READY
Autoreclose in service
AR LOCKOUT
Autoreclose in lockout status (finished cycled-definite trip)
AR BLOCK
Autoreclose blocked (by input, logic, others, etc).
AR RCL IN PROGRESS Cycle in course (autoreclose in progress).
AR LCK BY ANOMALY Autoreclose in "Lockout" by anomaly.
AR LCK BY FAIL OPEN Autoreclose in "Lockout" by failure to open
AR LCK BY FAIL CLOSEAutoreclose in "Lockout" by failure to close
AR LCK BY USER
Autoreclose in "Lockout" by user Command; manual breaker close during the autoreclose cycle
AR LCK BY CONDS
Autoreclose in lockout by non-compliance of the autoreclose conditions
AR LCK BY TRIPS
Autoreclose in "Lockout" by maximum number of trips (Lockout status not available)
AR LCK BY SHOTS
Autoreclose in "Lockout" at the end of cycle – Definite trip (due to Maximum Number of shots
reached).
AR BLK AFTER 1 SHOT Block signal sent by the autoreclose after the first shot
AR BLK AFTER 2 SHOT Block signal sent by the autoreclose after the second shot
AR BLK AFTER 3 SHOT Block signal sent by the autoreclose after the third shot
AR BLK AFTER 4 SHOT Block signal sent by the autoreclose after the fourth shot
AR BLOCK BY LEVEL
Autoreclose blocked by level. See AR block signals configuration (AR LEVEL BLOCK)
GE Multilin
Autoreclose.
These signals can be used as conditions for executing logics in the
AUTORECLOSE ENUMERATED STATUS
AR STATUS
AR READY
AR LOCKOUT
AR BLOCK
AR RCL IN PROGRESS
AR LOCKOUT MODE
AR LCK BY ANOMALY
AR LCK BY FAIL OPEN
AR LCK BY FAIL CLOSE
AR LCK BY USER
AR LCK BY CONDS
AR LCK BY TRIPS
AR LCK BY SHOTS
AR BLOCK MODE
AR BLOCK BY LEVEL
AR BLOCK BY PULSE
F650 Digital Bay Controller
5.5 CONTROL ELEMENTS
5-89
5

Advertisement

Table of Contents
loading

Table of Contents