2 PRODUCT DESCRIPTION
SELECTOR SWITCH
Number of elements:
2
Upper position limit:
1 to 7 in steps of 1
Selecting mode:
time-out or acknowledge
Time-out timer:
3.0 to 60.0 s in steps of 0.1
Control inputs:
step-up and 3-bit
Power-up mode:
restore from non-volatile memory or syn-
chronize to a 3-bit control input or synch/
restore mode
OSCILLOGRAPHY
Maximum records:
64
Sampling rate:
64 samples per power cycle
Triggers:
any element pickup, dropout, or operate;
digital input change of state; digital out-
put change of state; FlexLogic™ equa-
tion
Data:
AC input channels; element state; digital
input state; digital output state
Data storage:
in non-volatile memory
EVENT RECORDER
Capacity:
1024 events
Time-tag:
to 1 microsecond
Triggers:
any element pickup, dropout, or operate;
digital input change of state; digital out-
put change of state; self-test events
Data storage:
in non-volatile memory
CONTACT INPUTS
1000 Ω maximum
Dry contacts:
Wet contacts:
300 V DC maximum
Selectable thresholds:
17 V, 33 V, 84 V, 166 V
Tolerance:
±10%
Contacts per common return: 4
Recognition time:
< 1 ms
Debounce time:
0.0 to 16.0 ms in steps of 0.5
Continuous current draw:4 mA (when energized)
CONTACT INPUTS WITH AUTO-BURNISHING
Dry contacts:
1000 Ω maximum
Wet contacts:
300 V DC maximum
Selectable thresholds:
17 V, 33 V, 84 V, 166 V
Tolerance:
±10%
Contacts per common return: 2
Recognition time:
< 1 ms
Debounce time:
0.0 to 16.0 ms in steps of 0.5
Continuous current draw:4 mA (when energized)
Auto-burnish impulse current: 50 to 70 mA
Duration of auto-burnish impulse: 25 to 50 ms
GE Multilin
8-BIT SWITCH
Number of elements:
Input signals:
Control signal:
Response time:
DIGITAL ELEMENTS
Number of elements:
Operating signal:
Pickup delay:
Dropout delay:
Timing accuracy:
DATA LOGGER
Number of channels:
Parameters:
Sampling rate:
Trigger:
Mode:
Storage capacity:
DCMA INPUTS
Current input (mA DC): 0 to –1, 0 to +1, –1 to +1, 0 to 5, 0 to 10,
Input impedance:
Conversion range:
Accuracy:
Type:
RTD INPUTS
Types (3-wire):
Sensing current:
Range:
Accuracy:
Isolation:
IRIG-B INPUT
Amplitude modulation:
DC shift:
Input impedance:
Isolation:
C30 Controller System
2.2 SPECIFICATIONS
6
two 8-bit integers via FlexLogic™ oper-
ands
any FlexLogic™ operand
< 8 ms at 60 Hz, < 10 ms at 50 Hz
48
any FlexLogic™ operand
0.000 to 999999.999 s in steps of 0.001
0.000 to 999999.999 s in steps of 0.001
±3% or ±4 ms, whichever is greater

2.2.3 MONITORING

1 to 16
any available analog actual value
15 to 3600000 ms in steps of 1
any FlexLogic™ operand
continuous or triggered
(NN is dependent on memory)
1-second rate:
01 channel for NN days
16 channels for NN days
60-minute rate:
01 channel for NN days
16 channels for NN days

2.2.4 INPUTS

0 to 20, 4 to 20 (programmable)
379 Ω ±10%
–1 to + 20 mA DC
±0.2% of full scale
Passive
100 Ω Platinum, 100 & 120 Ω Nickel, 10
Ω Copper
5 mA
–50 to +250°C
±2°C
36 V pk-pk
1 to 10 V pk-pk
TTL
22 kΩ
2 kV
2