Honeywell rm7890a Installation Instructions Manual page 8

Microprocessor based integrated burner controls 7800 series
Hide thumbs Also See for rm7890a:
Table of Contents

Advertisement

RM7890A,B,C/EC7890A,B 7800 SERIES RELAY MODULES
L1
(HOT)
L2
1
MASTER
SWITCH
LED
DISPLAY
BURNER
START
OPERATING
CONTROLLER
AND LIMITS
FLAME
SIGNAL
1
120V, 50/60 HZ (RM7890) 220-240, 50/60 HZ (EC7890) POWER
SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
INSTALL A LINE VOLTAGE CONTROLLER IN SERIES WITH THE
LIMITS. IF USING A LOW VOLTAGE CONTROLLER IS
DESIRABLE, INSTALL AN EXTERNAL RELAY WITH THE N.O.
CONTACTS IN SERIES WITH THE LIMITS. THE LOW VOLTAGE
RELAY COIL WILL BE IN THE LOW VOLTAGE CONTROLLER
CIRCUIT. NOTE THAT IT MAY BE NECESSARY TO PROVIDE
AN EXTERNAL LOW VOLTAGE TRANSFORMER.
3
DO NOT CONNECT ANY WIRES TO UNUSED TERMINALS.
TERMINAL 22 IS ONLY ON THE RM/EC7890B.
4
5
FOR CONTINIOUS OR STANDING PILOT, USE THE RM7890C.
WHEN USING RM/EC7890A OR B; INSTALL AN EXTERNAL
RELAY TO SWITCH THE F LEAD. THE RELAY MUST HAVE
GOLD-CLAD OR GOLD-FLASH CONTACTS AND A LINE
VOLTAGE COIL. POWER THE RELAY COIL FROM THE Q7800
SUBBASE TERMINAL 8. CONNECT THE RELAY CONTACTS
BETWEEN THE F LEAD OF THE DETECTOR AND THE F
TERMINAL OF THE Q7800 SUBBASE. THE R4222N1002 OR
R4222V1002 RELAY IS ACCEPTABLE TO USE IN THIS TYPE OF
APPLICATION. USE THE N.O. PILOT DUTY CONTACTS.
66-1089—11
LINE VOLTAGE
ALARM
2
BURNER
CONTROLLER/LIMITS
INTERMITTENT
PILOT/IGNITION
MAIN FUEL
VALVE(S)
IGNITION
FLAME DETECTOR
7
6
INITIATE
STANDBY
POWER
POWER
SAFE START CHECK
Fig. 2. Wiring subbase and operating sequence chart for RM/EC7890.
Q7800
G
12
L2
13
14
3
(L1)
4
15
5
16
6
17
7
18
8
19
20
9
21
10
F
22
5
00
00
4/10
8
SAFE-
PFEP
MFEP
START
4 OR 10 SEC
POWER
POWER
POWER
PILOT
PILOT
FLAME
FLAME
MAIN
MAIN
ALARM
ALARM
10
IGNITION
9
INTERMITTENT PILOT
MAIN VALVE
LIMITS AND BURNER CONTROL CLOSED
FLAME PROVING
6
USING EC7890, A 220-240 VAC TO 120 VAC, 10 VA MINIMUM
STEP-DOWN TRANSFORMER (NOT PROVIDED) MUST BE
USED TO DRIVE THE SHUTTER (C7012E,F; C7061; C7076A,D
DETECTORS).
7
SEE FLAME DETECTOR SPECIFICATION FOR CORRECT WIRING.
8
RM7890A1031 PFEP IS 30 SECONDS FIXED. RM7890B1030 PFEP IS
10 SECONDS FIXED.
9
MAIN FUEL VALVE IS ENERGIZED AND IGNITION (TERMINAL 10) IS
TURNED OFF DURING PFEP ONCE FLAME IS PROVEN.
EXCEPTIONS:
RM7890A1031 HAS A FIXED 30 SECOND PFEP
RM7890B1030 HAS A FIXED 10 SECOND PFEP
RM7890A1064, RM7890B1055 AND EC7890A1037
JR1 INTACT – 10 SECOND FIXED PFEP, IGNITION
(TERMINAL 10) SHUTS OFF AT 6 SECONDS.
JR1 CLIPPED – 4 RECONDS FIXED PFEP, IGNITION
(TERMINAL 10) SHUTS OFF AT 2 SECONDS.
8
FOR DIRECT SPART IGNITION
(OIL OR GAS)
IGNITION
10
TRANSFORMER
8
MAIN VALVE
9
3
4
20
RUN
STANDBY
POWER
POWER
PILOT
FLAME
MAIN
ALARM
8
9
9
3
6
TO
S S C
M23305C
L2