Function Prompt
Lower Display
CUR OUT
LOW VAL
HIGH VAL
CO RANGE
12/04
Selections or
Range of Setting
Upper Display
DISABLE
INPUT 1
INPUT 2
PV
DEV
OUTPUT
SP
LSP
RSP
IN ALG 1
Low Scale Value within
the range of the selected
variable to represent the
minimun output (0 or 4
mA)
High Scale Value within
the range of the selected
variable to represent the
maximum output (20 mA)
4-20mA
0-20mA
UDC3200 Universal Digital Controller Product Manual
Parameter
Definition
CURRENT OUTPUT – If Current Output #1 is not
used to perform one of the above output algorithms,
it may be used to perform an Auxiliary Output
function.
DISABLE
INPUT 1
INPUT 2
PV (Process Variable)
DEVIATION
OUTPUT
SETPOINT
LOCAL SETPOINT
REMOTE
INPUT ALGORITHM 1
CURRENT OUTPUT LOW SCALING FACTOR—
Used only when CUR OUT is any selection other
than DISABLE. This is a value in engineering units
used to represent all CUR OUT parameters except
Output.
For Output, this is a value in percent and can be any
value between –5 % and +105 %. However, keep in
mind that relay output types can only be scaled 0 %
to 100 %.
CURRENT OUTPUT HIGH SCALING FACTOR—
Used only when CUR OUT is any selection other
than DISABLE. This is a value in engineering units
used to represent all CUR OUT parameters except
Output.
For Output, this is a value in percent and can be any
value between –5 % and +105 %. However, keep in
mind that relay output types can only be scaled 0 %
to 100 %.
CURRENT OUTPUT RANGE allows the user to
easily select 4-20 mA output or 0-20 mA output
operation without the need for recalibration of the
instrument.
ATTENTION Changing the Current Output Range
will result in the loss of Field Calibration values and
will restore Factory Calibration values.
Configuration
63