Shelf: J2007001 L014 CC109157657
DC input from left and right
L015 150042727
DC input from left only
Converters: CP2000DC54PEZ CC109162104
CP2500DC54PEZ CC109170528
Controller:
CP841_3C3R
No vertical spacing is required, allow a minimum 2 inch clearance at back of shelf for rectifier airflow.
Refer to Compact Power Line (CPL) Brochure for details and accessories.
Tools required:
Wire cutters and strippers
Cable crimpers
Step 1 - Mount Shelf
1. Reposition mounting ears as required - 8 screws each.
Torque to 25 in-lb (2.8Nm) - Phillips screwdriver.
2. Attach shelf to the frame using a minimum of four screws (two
on each side) - 12-24 (provided).
Torque to 35 in-lb (4Nm) - 5/16" socket.
Step 2 - Connect Chassis Ground
Some applications may rely on frame mounting screws for shelf
ground omitting the chassis ground cable.
Minimum 6 AWG wire is recommended.
Lugs - 1/4" on 5/8" centers (not provided).
Torque to 65 in-lb (7.3 Nm) - 7/16" socket.
Output Return (Ground)

Quick Start Guide

CC109145331
Torque wrench - 0-65 in-lb (0-10Nm)
Sockets - 5/16", 7/16, etc.
-48V Output
4
POS
3
(L015 has all DC input feeds from the right as viewed from the rear)
CP Converter Shelf - Quick Start Guide
Document 850033106 r04 2015 April
Step 3 - Connect -48V Output and Output Return
Lugs - 1/4" on 5/8" centers (not provided).
Torque to 65 in-lb (7.3 Nm) - 7/16" socket.
Step 4 - Connect DC Inputs

Feed each input from 80A breaker (shelf rating limited)
Lugs - 1/4" on 5/8" centers (not provided).
Torque to 65 in-lb (7.3 Nm) - 7/16" socket
CAUTION: Verify DC Input voltage and polarity with a voltmeter
before proceeding.
Note: Input Feed Returns must be externally connected to DC
Reference (CO) ground.
DC Inputs - Converter Inputs
NEG
NEG
L014 shown
Screwdrivers - Philips #1 and #2, Flat small
1
Chassis
POS
Ground
2
1

Advertisement

loading

Summary of Contents for GE CP2000DC54PEZ

  • Page 1: Quick Start Guide

    CP Converter Shelf System –48V Shelf: J2007001 L014 CC109157657 DC input from left and right L015 150042727 DC input from left only Converters: CP2000DC54PEZ CC109162104 CP2500DC54PEZ CC109170528 Controller: CP841_3C3R CC109145331 No vertical spacing is required, allow a minimum 2 inch clearance at back of shelf for rectifier airflow.
  • Page 2 J4 1-Wire Battery Temp and Voltage Monitor J1 Alarms and Inputs - page 4 J5 LAN Port RS-232 Craft port J2 External Alarm Inputs - page 4 J7 External Distribution Shelf.- page 4 Signal Connections Step 5 - Set Jumpers - LAN Port and Relay per Galaxy Pulsar Edge Controller Quick Start Guide Step 6 - Install Controller per Galaxy Pulsar Edge Controller Quick Start Guide Step 7 - Install Signal and Communications Cables Connectors are on rear.
  • Page 3 Information: Alarm Connections See the Compact Power Line Brochure for details. Alarm connections are on the rear of the shelf - J1 is Alarm Outputs and J2 is Alarm Inputs. Change alarm descriptions via LAN port (Web pages) or Craft port (EasyView2) when required. Connector J1 - Controller Variants J2 - All Controllers...
  • Page 4 Galaxy Pulsar Edge Quick Start Guide CC848836981 Galaxy Pulsar Edge Controller Family Product Manual Compact Power Line (CPL) Brochure CP Converter Shelf - Quick Start Guide GE ● 601 Shiloh Rd. ● Plano, TX 75074 ● 1- 888-546-3243 Document 850033106 r04 2015 April www.gecriticalpower.com...

This manual is also suitable for:

Cp2500dc54pez