Mode Number
(Press i key
to change)
Select
Temperature
34
range stops in
heating (T7100F
only).
Temperature
35
range stops in
cooling (T7100F
only).
Not used.
36
Temperature
37
display
adjustment.
Minimum Off
38
times in heating.

INSTALLER SELF-TEST

Use the Installer Self-Test to check the thermostat
configurations and operation. Refer to Table 3 for a list of
the available Self-Tests.
NOTE: The minimum Off time for compressors is
bypassed during the Installer Self-Test.
To start the Self-Test:
Press and hold the increase
the same time, until two zeros appear. All segments of
the LCD are displayed for three seconds before the two
zeros appear. Refer to Fig. 6 and 7.
Em Ht Temporary Setting
Aux Ht
Repl
Wait
Batt
System
Em HeatOffCool Auto Only
Fig. 6. Display of all LCD segments.
T7100F MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
Table 2. Thermostat Installer Setup Options (Continued).
Factory-Setting
Display
90
Highest heating setpoint
allowed.
45
Lowest cooling setpoint
allowed.
00
No difference in
displayed temperature
and actual room
temperature.
02
2-minute minimum Off
time.
and decrease
keys, at
Remote
Room
%Humid
Outdoor
Heat Cool
Fan
OnAuto
M4844
Description
Display
40 - 89
46 - 99
01 - 06
00, 01,
03, 04 or
05
Fig. 7. Display of Test Mode number.
Table 3. Installer Self-Test Mode Tests.
Test
Number
10-19
Heating equipment can be turned on and off.
20-29
Emergency heat (Q7100C only) equipment
can be turned on and off.
30-39
Cooling equipment can be turned on and off.
40-49
Fan equipment can be turned on and off.
60-69
Keyboard keys test.
70-79
Thermostat information including date code
and software versions is displayed.
Refer to Table 4 for the directions and results of the
specific tests.
NOTE: Press and hold the increase
keys for three seconds to exit the Self-Test
mode. Self-Test times out after five minutes
without any key presses.
5
Other Choices
(Press
or
key to change)
Description
Temperature range for (1°F
increments) heating setpoint.
Temperature range for (1°F
increments) cooling setpoint.
01—Display adjusts to 1°F higher
than actual room temperature.
02—Display adjusts to 2°F higher
than actual room temperature.
03—Display adjusts to 3°F higher
than actual room temperature.
04—Display adjusts to 1°F lower
than actual room temperature.
05—Display adjusts to 2°F lower
than actual room temperature.
06—Display adjusts to 3°F lower
than actual room temperature.
Minimum number of minutes (0
thru 5) the heating equipment is off
between calls for heat.
TEST MODE
NUMBER
Self-Test Description
and decrease