Siemens 125-2134 Owner's Manual page 26

Differential pressure monitor
Table of Contents

Advertisement

Differential Pressure Monitor Owner's Manual
Descriptor
Address
MID1 NEG
56
MIN1 NEG
57
SIG1 PHASE
67
DP1 RAW
68
MAX2 POS
71
MID2 POS
72
MIN2 POS
73
ZERO 2
74
MAX2 NEG
75
MID2 NEG
76
MIN2 NEG
77
SIG2 PHASE
87
16
Application
701, 702,
Represents the field calibration differential pressure, as read from
703, 704
DP1 RAW (Point 68), when the Remote Pressure Transmitter
calibrator is set to the MIDdle differential pressure (-0.050 in. of
water, -12.45 Pascals) for negative pressurization.
701, 702,
Represents the field calibration differential pressure, as read from
703, 704
DP1 RAW (Point 68), when the Remote Pressure Transmitter
calibrator is set to the MINimum differential pressure (-0.005 in.
of water, -1.24 Pascals) for negative pressurization.
701, 702,
When calibrating the sensor, the direction of flow through the
703, 704
sensor needs to be verified. If DIFF PRES1 (Point 30) is reading
a negative value when it should read positive, and this point is
set to LO, toggle the point from LO to HI.
701, 702,
Indicates RAW counts used for diagnostic purposes.
703, 704
702, 704
Represents the field calibration differential pressure, as read from
DP2 RAW (Point 88), when the Remote Pressure Transmitter
calibrator is set to the MAXimum differential pressure (+0.170 in.
of water, 42.34 Pascals) for positive pressurization.
702, 704
Represents the field calibration differential pressure, as read from
DP2 RAW (Point 88), when the Remote Pressure Transmitter
calibrator is set to the MIDdle differential pressure (+0.050 in. of
water, 12.45 Pascals) for positive pressurization.
702, 704
Represents the field calibration differential pressure, as read from
DP2 RAW (Point 88), when the Remote Pressure Transmitter
calibrator is set to the MINimum differential pressure (+0.005 in.
of water, 1.24 Pascals) for positive pressurization.
702, 704
Represents the field calibration differential pressure, as read from
DP2 RAW (Point 88), when tape is applied over the Remote
Pressure Transmitter through-the-wall ports producing a zero
differential pressure (+0.000 in. of water, 0.000 Pascals).
702, 704
Represents the field calibration differential pressure pulse
frequency, as read from DP2 RAW (Point 88), when the Remote
Pressure Transmitter calibrator is set to the MAXimum differential
pressure (-0.170 in. of water, -42.34 Pascals) for negative
pressurization. This value can be input directly by the operator or
can be input from the system.
702, 704
Represents the field calibration differential pressure, as read from
DP2 RAW (Point 88), when the Remote Pressure Transmitter
calibrator is set to the MIDdle differential pressure (-0.050 in. of
water, -12.45 Pascals) for negative pressurization.
702, 704
Represents the field calibration differential pressure, as read from
DP2 RAW (Point 88), when the Remote Pressure Transmitter
calibrator is set to the MINimum differential pressure (-0.005 in.
of water, -1.24 Pascals) for negative pressurization.
702, 704
When calibrating the sensor, the direction of flow through the
sensor needs to be verified. If DIFF PRES2 (Point 31) is reading
a negative value when it should read positive, and this point is
set to LO, toggle the point from LO to HI.
Description
Siemens Building Technologies, Inc.