Special installation (When the display is put in a box)
3.5.4 When the display is put in a box
Operating this display in confined spaces is not recommended.
• If the display is to be used in confined spaces, observe the following conditions shown in the drawing below in this page:
A ≥ 50
B ≥ 50
C ≥ 10
D ≥ 50
Use a mesh with aperture efficiency of 50% or more.
Thus, everywhere in "Y" must be kept less than the following temperature range. If hot air remains in the closed
space, the temperature may rise, causing a malfunction or fire. As a precaution in case of accidents, the inner wall
should have sufficient heat resistance or fire resistance.
✩ Usage temperature conditions (BOX air temperature)
• Ambient temperature: 0 to 35 °C
Rear view (the following area should be made of mesh)
+50 mm
Exhaust
side
A
A
1118 mm or more
+50mm
A
1118 mm or more
Outside air temperature mea-
suring point
10mm
Intake
side
A
Mesh with aperture efficiency
of 50% or more
A
+50mm
A
+50 mm
[503CMX/503MXE]
A ≥ 50
B ≥ 50
C ≥ 10
D ≥ 50
10mm
C
D
41