1MRK500127-UUS Rev. M
IEC18000088 V1 EN-US
Figure 47:
3.
Click on the Yes button to confirm the deletion.
The through fault reports are deleted from the IED, and a confirmation dialog box appears.
IEC18000089 V1 EN-US
Figure 48:
Exporting through fault reports files
Proceed as follows to export through fault reports files from the IED via PCM600:
1.
Click on the export reports
A confirmation message appears upon exporting the through fault reports files from an IED.
IEC18000090 V1 EN-US
Figure 49:
The through fault reports are exported into PCMDataBases folder as shown in
670 series
Operation manual
Confirm clear through fault reports
Clear through fault reports confirmation window
In order to delete through fault reports for all function instances from an IED, select All option
from the through fault monitoring selection combo box.
Authentication pop-up dialog box is displayed if external users (CAM/UAM) are defined in
the IED. The roles with IEDCmd – Advanced right are allowed to clear through fault reports
from an IED via PCM600.
option from the tool bar to export report files from the IED.
Export reports confirmation window
© 2017 - 2023 Hitachi Energy. All rights reserved
IEC18000088-1-en.vsdx
IEC18000089-1-en.vsdx
IEC18000090-1-en.vsdx
Section 7
Operating procedures
GUID-63BAF274-FC37-4416-819B-D9973FC103F4 v1