Features; Maintenance; Installation; Mechanical Requirements - LG HBP 16H Installation Manual

Table of Contents

Advertisement

1. Short Circuit Current/Duration
Short Circuit Current
1.616 kA
Duration
0.44 ms
2. Arc Flash Protection Calculations
Calculations refer to Annex D of NFPA 70E.
Battery System Voltage
288.4V
Battery System Internal Resistance
Bolted Fault Current
1.616 kA
Arcing Current
0.808 kA
Clearing Time
371 us
Arc Flash Incident Energy
0.000132 Cal/cm
Working Distance
450 mm (18inches)
Battery system installers must wear PPE (Personal Protective Equipment) according to
NFPA 70E Article 130.
WARNING
When installing the battery system, the worker shall wear arc-rated clothing
in every occasions and places to protect him/her from any possible exposure
The arc-rated clothing worn by the worker must assure the worker's
movement and visibility while covering all ignitable clothing.
The worker shall always wear the non-conductive safety helmet every
occasions and places to protect him/her from any danger of head injury
from electric shock or burns due to the contact with energized electrical
conductors or circuit parts resulting from electrical explosion.
The worker shall wear non-conductive protective equipment for the face,
neck, and chin at every occasion and location to protect him/her from danger
explosion.
The worker shall wear non-conductive protective equipment for the eyes at
every occasion and location to protect him/her from any danger of injury
The worker shall wear heavy-duty leather gloves or arc-rated gloves,
of wearing the rubber gloves for the shock protection, he/she shall wear
additional leather protectors above the gloves.
The worker shall wear heavy-duty leather footwear or dielectric footwear or
The worker shall inspect arc-rated apparel before every use. Work clothing
the protective qualities, shall not be used. Protective items that become
shall not be used.
The garment manufacturer's instructions for care and maintenance of arc-
rated apparel shall be followed.
Arc-rated apparel shall be stored in a manner that prevents physical damage;
damage from moisture, dust, or other deteriorating agents; or contamination

2.2 Features

Compact energy storage unit for domestic photovoltaic system compatibility
Residential 400V DC battery pack system: Daily cycle and emergency back up
capability.
+
Battery
DC/DC
-
Battery Power
Interface
Protection devices included as follows:
- Inverter Power Interface for protection against overvoltage, overcurrent, external
short-circuit, reverse polarity, inrush current and over temp.
- Battery Power Interface for protection against internal short-circuit, overvoltage,
overcurrent, over temp and undervoltage.
Flexible installation: Indoors or Outdoors
2
Circuit Breaker
+
Inverter
Circuit
Breaker
(600V)
-
Inverter Power
Interface

2.3 Maintenance

BLG RESU16HP does not require maintenance during normal operation if properly installed
per the installation manual. In the event of fault, contact the regional service center.
Category
Contents
750 mm
985 mm
Size (L×W×H)
(29.5")
(38.8")
Qty/Box (ea)
1
Box
Corrugated Cardboard
Packaging
Inner
EPS
Materials
Pallet
Wood
Product
159 kg (350.5 lbs)
Weight
Packaging
30 kg (66.1 lbs)
Gross
189 kg (416.7 lbs)

3 Installation

3.1 Mechanical Requirements

3.1.1

Package Contents

The following items are included in the package:
Battery Module A&B Battery Control Unit
Standing Bracket
Spacer (x2)
1 & 2
3/4"-1" Adapter (x2)
Cap (x2)
Cable ties
885 mm
Outer Size
(34.8")
Disposable
Disposable
Disposable
1 pack/box
(Battery Module (x2) + Battery
Control Unit + enclosed items)
Pallet (8.7kg) + Box (21.3kg)
Product + Packaging
Module Connect
Module Support
Plate
BRKT (x2)
M6 x L10 Flange
M5 × L200 Long
Bolt (x18)
Flange Bolt (x6)
Manual
Drill template
5

Advertisement

Table of Contents
loading

This manual is also suitable for: