1MRK 511 409-UUS Rev. K
10.8.3.1

Forcing by using LHMI

Editing a signal value directly
Edit the input/output value directly to select the desired logical level, by doing following:
1.
2.
3.
When navigating away from a LHMI forcing menu for an I/O board, the user is prompted to either leave
the signals forced, or to revert all of them back to the unforced state.
IEC15000022 V1 EN-US
Phasor measurement unit RES670
Commissioning manual
Select the value line of the desired signal, see figure 21.
Press the Enter key to edit the value.
IEC15000021 V1 EN-US
Figure 21:
Value line of the desired signal
Use the up/down arrows on the LHMI to change the signal value or the appropriate menu in
PCM600.
The status of the signal changes automatically to Forced (i.e. there is no need to set the status
to Forced manually).
On the LHMI, these edit changes have immediate effect. This means that the value
changes directly when the up/down arrow is pressed (i.e. there is no need to press the
Enter key to effectuate the change).