Indroopvaluesdcps[%]; Indefaultoperationmode[X] - Siemens SIMOCRANE Operating Instructions Manual

Energy storage system management v01.01
Table of Contents

Advertisement

5.1.8

inDroopValuesDCPs[%]

The SINAMICS DCPs are connected in parallel in the energy storage system to increase power.
Droop control makes parallel connection possible. The droop value determined by the energy
storage system [%] (p.54127) must be signaled to SIMOCRANE ESSM. This causes a voltage
correction to be applied which is dependent on the actual system power. This is necessary in
order to compensate for voltage fluctuations in the DC link due to operation in droop control.
Table 5-28
Input
inDroopValuesDCPs[%]
Unwanted reactions in the control response
The droop value must be an exact match for the droop value determined by the system
(p.54127), as unwanted reactions in the control response are otherwise possible.
Note
Details about parallel connection
You can find details about the parallel connection of SINAMICS DCPs via the droop control in the
operating instructions: SINAMICS DCP DC power converter
support.industry.siemens.com/cs/ww/en/view/109773591).
5.1.9

inDefaultOperationMode[X]

This input can be used for configuring the standardized operating mode after startup of the ESS
IF PLC:
• 1 = "Manual"
• 2 = "Black Start"
• 3 = "Peak Shaving"
Table 5-29
Input
inDefaultOperationMode[X]
SIMOCRANE Energy Storage System Management V01.01
Operating Instructions, 04/2023, A5E51573536B AE
inDroopValuesDCPs[%]
CAUTION
inDefaultOperationMode[X]
Data type
Real
Data type
Integer
Block interface
Comment
Value for droop control
(https://
Comment
The system starts with this oper‐
ating mode by default.
5.1 Inputs
49