Download Print this page

Toshiba GR-200 Series Instruction Manual page 221

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Setting
2.18.7
Setting of OVN_MV (Function ID: 464181)
Setting device
OVN1-EN
OVN2-EN
OVN3-EN
OVN4-EN
OVN1
OVN1-Timer
DT
OVN1
TOVN1
OVN1-DPR
IDMT
OVN1
OVN1-DPR
OVN1-TMS
TOVN1R
ORG
OVN1
OVN1-DPR
OVN1-TMS
TOVN1R
Output
OVN1-VTFBlk
OVN1-UseFor
OVN2
OVN2-Timer
DT
OVN2
TOVN2
OVN2-DPR
IDMT
OVN2
OVN2-DPR
OVN2-TMS
TOVN2R
ORG
OVN2
OVN2-DPR
OVN2-TMS
TOVN2R
Output
OVN2-VTFBlk
OVN2-UseFor
OVN3
OVN3-Timer
DT
OVN3
TOVN3
OVN3-DPR
IDMT
OVN3
OVN3-DPR
OVN3-TMS
TOVN3R
ORG
OVN3
OVN3-DPR
OVN3-TMS
TOVN3R
Output
OVN3-VTFBlk
OVN3-UseFor
OVN4
OVN4-Timer
DT
OVN4
TOVN4
OVN4-DPR
IDMT
OVN4
Range
Unit
Off / On
- OVN1 protection scheme switch
Off / On
- OVN2 protection scheme switch
Off / On
- OVN3 protection scheme switch
Off / On
- OVN4 protection scheme switch
DT / IDMT / Original
- OVN1 delay type
1.0 - 220.0
V OVN1 threshold
0.00 - 300.00
s OVN1 operating delay time (in DT mode)
10 - 100
% OVN1 drop-out/pick-up ratio
1.0 - 220.0
V OVN1 threshold
10 - 100
% OVN1 drop-out/pick-up ratio
0.010 - 100.000
- OVN1 time multiplier (in IDMT mode)
0.0 - 300.0
s OVN1 definite time reset delay
1.0 - 220.0
V OVN1 threshold
10 - 100
% OVN1 drop-out/pick-up ratio
0.010 - 100.000
- OVN1 time multiplier (in ORG mode)
0.0 - 300.0
s OVN1 definite time reset delay
Non / Block
- OVN1 operation block by VTF
Trip / Alarm
- OVN1 used for trip or alarm
DT / IDMT / Original
- OVN2 delay type
1.0 - 220.0
V OVN2 threshold
0.00 - 300.00
s OVN2 operating delay time (in DT mode)
10 - 100
% OVN2 drop-out/pick-up ratio
1.0 - 220.0
V OVN2 threshold
10 - 100
% OVN2 drop-out/pick-up ratio
0.010 - 100.000
- OVN2 time multiplier (in IDMT mode)
0.0 - 300.0
s OVN2 definite time reset delay
1.0 - 220.0
V OVN2 threshold
10 - 100
% OVN2 drop-out/pick-up ratio
0.010 - 100.000
- OVN2 time multiplier (in ORG mode)
0.0 - 300.0
s OVN2 definite time reset delay
Non / Block
- OVN2 operation block by VTF
Trip / Alarm
- OVN2 used for trip or alarm
DT / IDMT / Original
- OVN3 delay type
1.0 - 220.0
V OVN3 threshold
0.00 - 300.00
s OVN3 operating delay time (in DT mode)
10 - 100
% OVN3 drop-out/pick-up ratio
1.0 - 220.0
V OVN3 threshold
10 - 100
% OVN3 drop-out/pick-up ratio
0.010 - 100.000
- OVN3 time multiplier (in IDMT mode)
0.0 - 300.0
s OVN3 definite time reset delay
1.0 - 220.0
V OVN3 threshold
10 - 100
% OVN3 drop-out/pick-up ratio
0.010 - 100.000
- OVN3 time multiplier (in ORG mode)
0.0 - 300.0
s OVN3 definite time reset delay
Non / Block
- OVN3 operation block by VTF
Trip / Alarm
- OVN3 used for trip or alarm
DT / IDMT / Original
- OVN4 delay type
1.0 - 220.0
V OVN4 threshold
0.00 - 300.00
s OVN4 operating delay time (in DT mode)
10 - 100
% OVN4 drop-out/pick-up ratio
1.0 - 220.0
V OVN4 threshold
- 202 -
Contents
6F2T0200 (0.15)
Default
Note
Off
Off
Off
Off
DT
120.0
1.00
100
120.0
100
1.000
0.0
120.0
100
1.000
0.0
Non
Trip
DT
120.0
1.00
100
120.0
100
1.000
0.0
120.0
100
1.000
0.0
Non
Trip
DT
120.0
1.00
100
120.0
100
1.000
0.0
120.0
100
1.000
0.0
Non
Trip
DT
120.0
1.00
100
120.0
GRE200 (1,2)

Advertisement

loading

This manual is also suitable for:

Gre200-1Gre200-2