Download Print this page

Toshiba GR-200 Series Instruction Manual page 971

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

ASCI basic conformance statement
The basic conformance statement is defined in Table A.1.
Client-Server roles
Server side (of TWO-PARTY-APPLICATION-
B11
ASSOCIATION)
Client side of (TWO-PARTY-APPLICATION-
B12
ASSOCIATION)
SCSMs supported
B21
SCSM: IEC 61850-8-1 used
B22
SCSM: IEC 61850-9-1 used
B23
SCSM: IEC 61850-9-2 used
B24
SCSM: other
Generic substation event model (GSE)
B31
Publisher side
B32
Subscriber side
Transmission of sampled value model (SVC)
B41
Publisher side
B42
Subscriber side
- = not applicable
Y = supported
N or empty = not supported
Table A.1 – Basic conformance statement
- 952 -
Client/
Server/
Subscriber
Publisher
Y
N
Y
Y
Y
Y
N
N
6F2T0200 (0.15)
(PICS Ed.1&Ed.2)
Value/
Comments
Client/Subscrib
er side is only
GOOSE
and
SNTP.
Deprecated
Ed2
GRE200 (1,2)

Advertisement

loading

This manual is also suitable for:

Gre200-1Gre200-2