6.3

Installing the standard rail adapter

Introduction
Use the standard rail adapter to mount the redundant SIMATIC S7-1500R/H-system on the
standardized 35 mm rails.
You order the DIN rail adapter as separate accessories.
NOTE
Note the following reduced technical specifications regarding mechanical load when
you install the S7-1500R/H modules on the 35 mm standard mounting rail using the
standard mounting rail adapter:
Vibration test acc. to IEC 60068-2-6 (sinusoidal)
• 5 Hz ≤ f ≤ 8.4 Hz, constant amplitude 3.5 mm
• 8.4 Hz ≤ f ≤ 150 Hz, constant acceleration 1 g
Duration of vibration: 10 frequency sweeps per axis in each of three perpendicular axes
Shock, tested according to IEC 60068-2-27
• Type of shock: Half-sine
• Shock intensity: 150 m/s
• Direction of shock: 3 shocks each in +/- direction, along each of the 3 perpendicular axes
Article No.
6ES7590-6AA00-0AA0
The scope of delivery consists of ten adapters, ten hexagon socket-head screws and ten
washers.
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
2
peak value, 11 ms duration
6.3 Installing the standard rail adapter
Installation
159