Failure Of The Two Profinet Cables In The Profinet Ring At The Primary Cpu - Siemens SIMATIC S7-1500 System Manual

Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Application planning
5.5 Failure scenarios
3. The primary CPU also fails. Due to the failure, the primary CPU is no longer visible for the
backup CPU.
4. The redundant system does not switch to the backup CPU, but switches to the STOP
system state. The role of the backup CPU remains unchanged.
NOTE
The backup CPU cannot distinguish between the following scenarios:
– It can no longer access the primary CPU because the latter has failed.
– The other redundancy connection has also been interrupted and the primary CPU may
That is why the backup CPU does not become the primary CPU. This prevents an
undefined system state.
5. System redundancy has failed. The process is no longer controlled by the redundant
system.
Diagnostics
System state and operating states after the failure of the redundancy connection and primary
CPU:
• Redundant system → STOP system state
• Primary CPU → failed
• Backup CPU → STOP operating state
– MAINT LED → yellow light: The H-system is not in the RUN-Redundant system state. No
NOTE
To get detailed diagnostics information, evaluate the diagnostics buffer.
Solution
Replace the defective redundancy connection and the primary CPU. You can find additional
information on the procedure in the sections Replacing defective redundancy connections
(Page 322) and Replacing defective R/H CPUs (Page 321).
5.5.4.3

Failure of the two PROFINET cables in the PROFINET ring at the primary CPU

Introduction
The following failure scenario describes the effects in case of a defect of both PROFINET lines
in the PROFINET ring at the primary CPU.
138
still be running.
partner CPU has been found in the H-system.
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1500rSimatic s7-1500h

Table of Contents