Quarterly Maintenance - Huawei UPS5000-E-12 User Manual

Table of Contents

Advertisement

UPS5000-E-(40 kVA-320 kVA)
User Manual
Content
Battery operating
temperature

6.2.3 Quarterly Maintenance

Table 6-6 Quarterly Maintenance
Item
Battery management alarm
Battery appearance
Battery operating
temperature
Issue 10 (2015-09-15)
Expected Results
1. The battery operating
temperature is lower
than 45° C.
2. The ambient battery
temperature is 25± 5° C.
Expected Result
No battery management
alarm is generated.
1. The battery shell is
intact, without acid
leaks, deformation, or
bulges.
2. The battery is free from
dust or dirt.
1. The battery operating
temperature is lower than
45° C.
2. The ambient battery
temperature is 25± 5° C.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 Routine Maintenance
Troubleshooting
remove faulty batteries. After 30
minutes, check and record the
open-circuit voltages of the faulty
batteries.
5. If the fault persists, contact Huawei
technical support.
1. Identify the cause of an abnormal
battery operating temperature.
2. If the fault persists, contact Huawei
technical support.
Troubleshooting
Identify the cause of an
alarm based on the alarm
information.
1. Take photos of the
deformed parts and
faulty parts of batteries.
2. Check and record the
charge voltage and
charge current of the
battery string, and the
voltage of every single
battery in this battery
string.
3. Check the battery surface
temperature.
4. Power off the battery
string and remove faulty
batteries. After 30
minutes, check and
record the open-circuit
voltages of the faulty
batteries.
5. If the fault persists,
contact Huawei technical
support.
1. Identify the cause of an
abnormal battery
operating temperature.
2. If the fault persists,
contact Huawei technical
200