Huawei UPS5000-E-12 User Manual page 194

Table of Contents

Advertisement

UPS5000-E-(40 kVA-320 kVA)
User Manual
Step 2 On the Settings screen, tap Intelli. Power. The Intelli. Power screen is displayed, as shown
in
Figure
Figure 5-48 Intelli. Power screen
Step 3 Set Intelligent power to Enabled. In the warning dialog box, tap Yes. The intelligent power
parameters are displayed, as shown in
Figure 5-49 Intelligent power parameters on the LCD
Issue 10 (2015-09-15)
5-48.
Intelligent Power Supply parameter
The value can be Enabled or Disabled. The intelligent power supply function is
available only if the value is Enabled. The default value is Disabled.
ATS parameter
The value can be Connected or Not connected. When the value is Connected, the UPS
works in the ATS scenario; when the value is Not connected, the UPS works in the reuse
scenario. The default value is Connected. This parameter is available only after you set
Intelligent Power Supply to Enabled.
D.G. startup batt. volt. (V/cell) parameter
The value ranges from 1.80 to 2.00. The default value is 1.80. This parameter is available
only after you set Intelligent Power Supply to Enabled.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure
5-49.
5 Operations
185

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-e-20Ups5000-e-3200k-f1200k-f200K-f320K-f320t

Table of Contents