C_PID
Name/target/control type/controls
RCU clear flags
Target: Line (Fusesaver all phases)
8
Control type: Unary control
Controls: Clear flags
Set protection mode - Normal
Target: Line (Fusesaver all phases)
9
Control type: Unary control
Controls: Set protection mode
Set protection mode - Fast single
Target: Line (Fusesaver all phases)
10
Control type: Unary control
Controls: Set protection mode
Set protection mode - Off
Target: Line (Fusesaver all phases)
11
Control type: Unary control
Controls: Set protection mode
Set protection mode - Normal single
Target: Line (Fusesaver all phases)
12
Control type: Unary control
Controls: Set protection mode
RCU - Reboot
Target: RCU
13
Control type: Unary control
Controls: Reboot
Set protection mode - Fast
Target: Line (Fusesavers all phases)
14
Control type: Unary control
Controls: Set protection mode
Set/clear protection off bit
Target: Line (Fusesavers all phases)
15
Control type: Binary control
Controls: Set/clear protection bit
Set/clear instantaneous protection bit
Target: Line (Fusesavers all phases)
16
Control type: Binary control
Controls: Set/clear protection bit
RCU database controls
This control clears the protection flags in the RCU (remote control unit).
This control issues commands to all phases to set their remote protection mode to normal
but only if communications are normal to each and every Fusesaver and no Fusesaver has
its external lever down. If communications have failed to any Fusesaver or any Fusesaver
has its lever down, then no command will be sent to any Fusesaver.
Controls will only be accepted if D_PID 101 (remote control enabled) is set. If not, then
control will be rejected with the relevant control response code.
This control issues commands to all phases to set their remote protection mode to fast
single but only if communications are normal to each and every Fusesaver and no
Fusesaver has its external lever down. If communications have failed to any Fusesaver or
any Fusesaver has its lever down, then no command will be sent to any Fusesaver.
Controls will only be accepted if D_PID 101 (remote control enabled) is set. If not, then
control will be rejected with the relevant control response code.
This control issues commands to all phases to set their remote protection mode to off but
only if communications are normal to each and every Fusesaver and no Fusesaver has its
external lever down. If communications have failed to any Fusesaver or any Fusesaver has
its lever down, then no command will be sent to any Fusesaver.
Controls will only be accepted if D_PID 101 (remote control enabled) is set. If not, then
control will be rejected with the relevant control response code.
This control issues commands to all phases to set their remote protection mode to normal
single but only if communications are normal to each and every Fusesaver and no
Fusesaver has its external lever down. If communications have failed to any Fusesaver or
any Fusesaver has its lever down, then no command will be sent to any Fusesaver.
Controls will only be accepted if D_PID 101 (remote control enabled) is set. If not, then
control will be rejected with the relevant control response code.
This control issues a reboot command to the RCU.
This control issues commands to all phases to set their remote protection mode to fast but
only if communications are normal to each and every Fusesaver and no Fusesaver has its
external lever down. If communications have failed to any Fusesaver or any Fusesaver has
its lever down, then no command will be sent to any Fusesaver.
Controls will only be accepted if D_PID 101 (remote control enabled) is set. If not, then
control will be rejected with the relevant control response code.
This control issues commands to all phases to set/clear their remote protection off bit but
only if communications are normal to each and every Fusesaver and no Fusesaver has its
external lever down. If communications have failed to any Fusesaver or any Fusesaver has
its lever down, then no command will be sent to any Fusesaver.
Controls will only be accepted if D_PID 101 (remote control enabled) is set. If not, then
control will be rejected with the relevant control response code.
This control issues commands to all phases to set/clear their instantaneous protection off
bit but only if communications are normal to each and every Fusesaver and no Fusesaver
has its external lever down. If communications have failed to any Fusesaver or any
Fusesaver has its lever down, then no command will be sent to any Fusesaver.
Controls will only be accepted if D_PID 101 (remote control enabled) is set. If not, then
control will be rejected with the relevant control response code.
Description