Siemens 3AD8 Instruction Manual page 27

Remote control unit (rcu)
Hide thumbs Also See for 3AD8:

Advertisement

D_PID
Phase
RCU - Fusesaver control panel line
controls enabled
Source: Remote control unit (RCU)
110
States: Fusesaver control panel line
controls enabled/Fusesaver control panel
line controls disabled
Event time tag: RCU time
RCU - Fusesaver control panel controls
allowed
Source: RCU
111
States: Fusesaver control panel line
controls allowed/Fusesaver control panel
line controls not allowed
Event time tag: RCU time
RCU - Fusesaver control panel present
Source: RCU
112
States: Fusesaver control panel present/
Fusesaver control panel not present
Event time tag: RCU time
Fusesaver - Remote protection mode -
fast
113
A
Source: Fusesaver
114
B
115
C
States: ‒/remote protection mode fast
Event time tag: RCU time
Fusesaver - In force protection mode -
fast
116
A
Source: Fusesaver
117
B
118
C
States: ‒/protection mode in force fast
Event time tag: RCU time
Fusesaver - Remote protection bit -
protection off
119
A
Source: Fusesaver
120
B
States: ‒/remote protection bit protection
121
C
off
Event time tag: RCU time
RCU database digital points list
Name/states/source
Status/events/restart/qualifiers
State: Set when the Fusesaver control panel controls are enabled for a line.
Cleared when the Fusesaver control panel controls are not enabled for a line.
Line controls are enabled when Fusesaver control panel controls are allowed
(refer to item 111 below) and the enable control button has been pressed (if
present).
The line controls can be disabled by pressing the enable control button, by time-
out or when Fusesaver control panel controls are not allowed (refer to item 111
below).
If the panel type is one which does not have enable controls button, then the
button is assumed to be on.
Events: Events generated by change of state above.
On restart: Volatile - state updated on restart.
Data qualifiers: Override, online.
State: Set when the Fusesaver control panel controls are allowed for a line.
Cleared when the Fusesaver control panel controls are not allowed for a line.
Fusesaver control panel controls are allowed if Fusesaver external levers and the
RCU switch are in the correct position, the Fusesavers are not being controlled
by Siemens Connect and the RCU is not in the process of updated the Fusesaver
time.
Events: Events generated by change of state above.
On restart: Volatile - state updated on restart.
Data qualifiers: Override, online.
State: Set when the RCU detects that a known Fusesaver control panel is
connected. Cleared when the RCU cannot detect a known Fusesaver control
panel.
Events: Events generated by change of state above.
On restart: Volatile - state updated on restart.
Data qualifiers: Override, online.
State: Set when Fusesaver remote protection mode is set to fast. Cleared when
Fusesaver remote protection mode is set to normal, normal single, fast single or
off. This status data comes from the Fusesaver live-data stream.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override, online, restart, communications lost.
State: Set when Fusesaver in force protection mode is set to fast. Cleared when
Fusesaver in force protection mode is set to normal, normal single, fast single or
off. This status data comes from the Fusesaver live-data stream.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override, online, restart, communications lost.
State: Set when Fusesaver remote protection bit protection off mode is set.
Cleared when Fusesaver remote protection bit protection off is cleared. This
status data comes from the Fusesaver live-data stream.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override, online, restart, communications lost.
27