7.1.1

Protocol-Independent Parameters

PW1
High Byte
Code
[hex]
00
Job has been passed to RSS without error
01
Call R5REQ again
02
Change PLC program
03
Change protocol parameter
04
Execute R5INIT again
05
Execute R5REQ again
06
Execute R5CON again
07
Reload V.24 protocol
08
Check system configuration
1070 072 196-101 (00.06) GB
General Information Regarding BUEP-E and BUEP19E
Job activation of the protocol-independent parameter is done via the
R5REQ module.
Parameter
Word
PW1
This is where after each module call the error message is passed over. The
low byte contains the error code and the high byte the proposed PLC reac-
tion.
PLC reaction
Attribute
Description
W
Result of the job
Code
[hex]
00
Job has been passed to RSS without error
01
Job is already being processed
02
Job is in queue
03
Job is acknowledged, but not yet confirmed
04
Wrong channel number
05
Wrong RSS number
06
Wrong job number
07
Abortion of job not possible
08
No free job number on the RSS
10
RSS 0 not initialized
11
RSS 1 not initialized
12
RSS 2 not initialized
13
RSS 3 not initialized
14
RSS 4 not initialized
20
RSS 0 not listed in SK table
21
RSS 1 not listed in SK table
22
RSS 2 not listed in SK table
23
RSS 3 not listed in SK table
24
RSS 4 not listed in SK table
30
Communication error on the RSS
31
Communication error on the ZS
92
Invalid command parameter
D0
No protocol for channel 0 (V24 channel) loaded
D1
Job queue is full
Low Byte
Error code
7- -3