FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Step 5 Install a new air filter and secure it.
Step 6 Install the air filter fasteners.
Step 7 Choose Maint > Performance Maint on the home screen and clear the total
runtime of the air filter.
Step 8 Power on the device and tap Start on the home screen. Ensure that the device is
running properly without generating alarms.
----End
8.4.4 Replacing an Air Filter (FDC Scenario)
Prerequisites
●
●
Procedure
Step 1 On the controller home screen, tap Shutdown and turn off the device switch in
the PDF.
Exercise caution because the device is still energized after it is shut down on the
controller home screen.
Step 2 Replace the outdoor intake air filter. Remove the air filter fasteners and take out
the air filter from the end.
Figure 8-6 Replacing an air filter
Issue 01 (2021-01-30)
An air filter needs to be replaced.
A spare air filter of the same model is available and functional.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
8 System Maintenance
144