Huawei FusionCol8000-E240 User Manual page 114

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Paramete
r
Enable
teamwork
CAN
resistor
Teamwork
function
Networkin
g mode
Number
of air
conditione
rs in this
group
Issue 01 (2021-01-30)
Description
Sets the status of each
build-out resistor of smart
cooling products in
teamwork networking. This
parameter is available
when the CAN network
mode is used.
Indicates whether to enable
the teamwork function. If
no, the unit operates
independently. If yes, the
unit operates in a team
with other units.
Indicates the networking
mode for teamwork control.
The networking mode set
on the screen must be
consistent with the actual
networking mode.
Otherwise, the teamwork
control function will be
unavailable. If the
networking mode changes,
select the corresponding
networking mode on the
screen.
Sets the number of smart
cooling products in a group.
The value is an integer
ranging from 1 to 32.
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Configuration Rule
● Set this parameter
to No for non-
teamwork
scenarios.
● For teamwork
control, set this
parameter to Yes
for the first and
last smart cooling
products in the
network, and set
this parameter to
No for other smart
cooling products.
Set this parameter
based on onsite heat
load distribution.
Set this parameter to
CAN network. CAN
network refers to
CAN teamwork
networking.
Enter the total
number of smart
cooling products in
the group.
Default
Value
No
Disable
CAN
network
3
105

Advertisement

Table of Contents
loading