Master/Follower Using Analog Terminals
Introduction
There are several ways to configure two(or more) G7 drives to operate in master/follower mode. This
application note will walk you through the steps necessary to configure a G7 drive for master/Follower
follower operation using the FM analog output terminal on the master drive and the II analog input
terminal on the follower.
Connections
Programming (Master Unit)
Direct
Parameter Path
Access
F005
Program
Meter Terminal
Adjustment Parameters
Programming (Follower Unit)
Direct
Parameter Path
Access
F004
Program
Fundamental
Parameters
Selection
(46) Place the Master G7 in Local control mode
(47) Place the Follower G7 in Remote control mode
(48) Push Run button to start the Master drive
(49) Close F-CC to start the Follower drive
(50) Use the encoder dial to adjust frequency on Master drive
(51) The Mastger drive will ramp up to the set speed entered from the encoder dial
(52) The Follower drive will follow the Master drive speed
For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192