How to find your set point in Local Mode:
You need to know what the range of your transducer is in order to solve for the set point in the drive.
Here is an example:
Transducer range: 4 to 20mA
Pressure range of transducer: 0 to 5 inches
Range of Drive: 0 to 60 (Maximum Frequency set at 60 hz)
Desired set point: 1.5 inches
Set point entered in the drive
1
5 .
inches
=
5
inches
0
inches
So for this example you would enter 18 as your set point in the drive.
For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192
efesotomasyon.com -Toshiba inverter,drive,servo,plc
desired
(
pressureat
× 60 = 18
_
setpiont
_
pressure
20
mA
pressureat
4
mA
)
×
60
11