7 TROUBLESHOOTING
No. Error code
1
3621
Program error (Invalid Data Access)
2
3661
Program error (Data Access Protection)
3
3601
Program error (Data Page Fault)
4
3421
Program error (Invalid Inst. Access)
5
3461
Program error (Inst. Access Protection)
6
3401
Program error (Instruction Page Fault)
7
3031
Program error (Inst. Alignment Error)
8
3081
Program error (Privileged Instruction)
9
3041
Program error (Illegal Instruction)
10
3391
Program error (FP Program Error)
11
3471
Program error (Data Alignment Error)
12
5130
Undefined Macro
13
5110
Macro parameter error
14
5C70
WDT timeout error
15
3B70
Module error (Bus Target Abort)
16
5000
Module error (Invalid Interrupt)
17
5001
Module error (Undefined Invalid Interrupt)
18
5002
Module error (INTEVT Invalid Interrupt)
19
50F1
Module error (HERST Invalid Interrupt)
20
50F2
Module error (HERST2 Invalid Interrupt)
21
50F3
Module error (BUERRSTAT Invalid Interrupt)
22
50F6
Module error (NHPMCLG Invalid Interrupt)
23
50F7
Module error (ECC 2bit Master Invalid Interrupt) Memory ECC 2-bit serious-error status
24
50F8
Module error (RERRMST Invalid Interrupt)
25
50C1
Module error (NINTR Invalid Interrupt)
26
50B1
Module error (PUINTR Invalid Interrupt)
27
5051
Module error (RINTR Invalid Interrupt)
28
5031
Module error (LV3 INTST Invalid Interrupt)
29
5032
Module error (RQI6 INF Invalid Interrupt)
30
5011
Module error (RQI3 INT Invalid Interrupt)
31
5012
Module error (RQI3 Link Invalid Interrupt)
32
5013
Module error (RQI3 Module Invalid Interrupt)
33
7D01
Module error (INVALID EXCEPTION)
34
7D10
Module error (INVALID MAIN/SUB SWITCH
SETTING)
35
0114
Module error (INVALID MAC ADDRESS)
36
7D12
Module error (MAIN/SUB SWITCH SETTING
DUPLICATION)
37
7D13
Module error (ETHERNET LSI CHECK
ERROR)
38
7D14
Module error (SDRAM CHECK ERROR)
39
7D15
Module error (OS-ROM CHECKSUM ERROR) ROM checksum error (in CPMS)
40
7D16
Module error (LQE702 CANNOT BE
MOUNTED ON THE SAME MOUNT BASE
AS LQE500/LQE502/LQE701)

Table 7-2 Error Messages (1/2)

Error message
Data access error
Data access protection error
Data access page fault
Instruction access error
Instruction access protection error
Instruction access page fault
Instruction alignment error
Privileged-instruction error
Illegal-instruction error
Floating-point arithmetic error
Data alignment error
Undefined macro issued
Incorrect macro parameter used
Watchdog timer timeout
Bus target aborted
Invalid interrupt detected
Undefined invalid interrupt detected
INTEVT invalid interrupt detected
Serious-error invalid interrupt detected
Serious-error invalid interrupt of type 2
detected
Bus serious-error interrupt status invalid
Memory serious-error interrupt status
invalid
invalid
RERR interrupt status invalid
NINT status invalid
PUINT status invalid
RINT status invalid
Level-3 interrupt status invalid
RQI6 status invalid
RQI3 status invalid
RQI3 link status invalid
RQI3 module status invalid
Invalid exception detected
Main-/submodule setting switch
operation error
MAC address error
Duplicate setting of main-/submodule
setting switch
LANCE diagnosis error
SDRAM initialization error
A model LQE702 module is mounted on
the same mount base in conjunction with
a model LQE500/LQE502/LQE701
module.
LER
Meaning
LED
(Turned
off)
7-8
ERR
Required recovery action
LED
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Set the switch correctly.
Turned on Hardware item replacement
Blinking
Set the switch correctly.
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on Hardware item replacement
Turned on The module cannot be mounted
on the same mount base on which
a model LQE500/502/701 module
is mounted. Remove the model
LQE500/502/701 module from
the mount base.