⑤ Tighten the conductor probe with the dedicated mounting wrench.

Figure 8-55 Mounting the Conductor Probe on a Coaxial Cable

Tap connection installation is now completed.
<Reference> A test method for making sure of a correct connection is described below.
• The shield pressure-connecting pins should be shorted.
• When terminators are attached to both ends of a coaxial cable, the resistance between
the conductor probe and shield pressure-connecting pin should be 25 Ω.
However, if the system is already running, do not run the above checks because the
system may malfunction.
⑥ Insert the transceiver body into the tap connector. Accomplish centering so that the
shield pressure-connecting pin is perpendicular to the conductor probe.

Figure 8-56 Inserting the Transceiver Body into the Tap Connector

8-55