⑤ Soldering of pin contact
Thread solder
Pin contact

Figure 8-47 Coaxial Cable Shield Treatment and Pin Contact Soldering

⑥ Connector attachment
(6) Transceiver
(a) Transceiver (tap type) installation
The transceiver installation location and method vary with the installation site conditions.
Typical installation locations are enumerated below:
• Wall surface
• Under the floor (in a free-access pit)
• Above the ceiling or on a cable rack
• On the side toward a station
When installing the transceiver, observe the following precautions:
• When equipped with mounting feet, the transceiver can be installed on a floor and secured
with wood screws.
• When installing the transceiver above the ceiling or under the floor, you should position it
so as to provide ease of maintenance.
• When installing two or more transceivers, space them at intervals of 2.5 m (mount the
transceivers over the marks that are put at 2.5 m intervals on a coaxial cable).
(b) Applicable transceiver
For the transceiver recommended for use with the FL.NET module, see "8.5.1 Ethernet
component list."
Allow a clearance of 1 mm or more between the pin contact and the
insulating material. Take care not to cause the pin contact to bite into
the insulating material.

Figure 8-48 Coaxial Cable Connector Assembly

8-51
8 APPENDIXES