Conettix Universal Dual Path Communicator
When an enclosure tamper switch is connected to the B465 tamper circuit (TMPR connector),
opening the enclosure door is a fault.
USB Menu Location
[4] System Configuration > [4] Tamper > [2] Tamper sets Trouble LED and Output
8.5

Communication Failure Action

8.5.1

Comm Fail sends reports

Default: Enabled
Selections:
USB Menu Location
[4] System Configuration > [5] Communication Failure Action > [1] Comm Fail sends reports
8.5.2

Comm Failure sets Trouble Output

Default: Disabled
Selections:
USB Menu Location
[4] System Configuration > [5] Communication Failure Action > [2] Comm Fail sets Trouble
Output
8.5.3

Comm Failure removes Line 1 phone voltage

Default: Disabled
Selections:
When the B465 removes voltage from the PNL LINE 1 terminals (terminals for panel phone line
1), the control panel connected to the terminals creates a phone line failure event or a
communication failure event.
USB Menu Location
[4] System Configuration > [5] Communication Failure Action > [3] Comm Fail removes line 1
phone voltage
8.5.4

Comm Failure removes Line 2 phone voltage

Default: Disabled
Selections:
Bosch Security Systems, Inc.
Enabled - when there is a communication failure event, the B465 inserts a FAILURE TO
COMMUNICATE report (Contact-ID 354) at the top of the report queue. It is the first
report sent when communication restores.
Disabled - the B465 does not send FAILURE TO COMMUNICATE reports.
Enabled - when there is a communication failure event, the B465 sets the system trouble
output.
Disabled - the B465 does not set the system trouble output for communication failure
events.
Enabled - when there is a communication failure event, the B465 removes voltage to the
PNL LINE 1 terminals (terminals for panel phone line 1).
Disabled - the B465 does not remove voltage to the PNL LINE 1 terminals for
communication failure events.
Enabled - when there is a communication failure event, the B465 removes voltage to the
PNL LINE 2 terminals (terminals for panel phone line 2).
Disabled - the B465 does not remove voltage to the PNL LINE 2 terminals for
communication failure events.
Installation and Operation Manual
System Configuration | en
2017.11 | 05 | F.01U.311.207
75