Siemens SINAMICS S120 Commissioning Manual page 243

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Control Unit 320-2 PN during run-up
Table 5- 3
Control Unit CU320-2 – description of the LEDs during ramp-up
LED
Color
RDY
Red
COM
Orange
OPT
Orange
RDY
Red
COM
Red
RDY
Red
COM
Red
RDY
Red
COM
Orange
RDY
Red
RDY
Red
COM
Red
COM
Red
RDY
Red
COM
Red
RDY
Orange
Control Unit 320-2 PN during operation
Table 5- 4
CU320-2 PN Control Unit – description of the LEDs after powering up
LED
Color
RDY
Green
Red
Commissioning with Startdrive
Commissioning Manual, 12/2018, 6SL3097-5AA10-0BP0
Display
State, description, cause
Steady light
Hardware reset
Steady light
BIOS loaded
Flashing light 2 Hz
BIOS error: "An error occurred while loading the BIOS".
Steady light
Steady light
Loading firmware: RDY LED lights up red, COM LED flashes
orange without fixed frequency.
Flashing light
Steady light
Firmware has been loaded.
Flashing light 2 Hz
File error:
Steady light
Firmware has been checked. No CRC error detected.
Flashing light 0.5 Hz
Firmware has been checked. CRC error detected.
Steady light
Initializing firmware
Display
Description, cause, remedy
OFF
Electronics power supply is missing or outside permissible toler-
ance range.
Remedy: Check the power supply.
Continuous light
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
Flashing light
Commissioning/reset
0.5 Hz
Flashing light
Writing to the memory card
2 Hz
Flashing light with the
Indicates PROFIenergy energy-saving mode.
on/off ratio
0.5 s = On
3 s = Off
Flashing light
General errors
2 Hz
Remedy: Check parameterization / configuration data
Memory card not available or faulty.
Software on memory card not available or faulty.
Diagnostics
5.2 Diagnostics using LEDs
241

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents