ABB ACS580-01 Installation Supplement Manual page 19

Low voltage drives, main switch and emc c1 filter options +f278, +f316, +e223, ip55 frames r1 to r5
Hide thumbs Also See for ACS580-01:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 9
EN – Main switch and EMC C1 filter options installation supplement 19
Connect the power cables
See the figures in section
the step numbers.
1. Remove the rubber grommets from the cable entry.
2. Input cable I: Prepare the input cable according to the R1...R5 quick installation
and start-up guide of the drive. To connect the input cable, see the text below and
the figures in section
Tighten the screws to the torque given beside figure 2.
Ground the shield 360 degrees by tightening the clamp of the power cable
grounding shelf onto the stripped part of the cable (2a).
Note: Do not yet connect the phase connectors to the main switch or terminal
block (2b).
Connect the twisted shield of the cable and the additional PE conductor of the
cable (2c).
3. Remove the two screws of the main switch or terminal block stand platform.
4. Turn the main switch or terminal block stand platform aside to the left to make
room for installing the motor and possible brake resistor cable.
5. Motor cable: Connect the motor cable according to the R1...R5 quick installation
and start-up guide of the drive. See also figure 5 on page 261. Tighten the screws
to the torque given beside the figure.
6. Install the grounding shelf.
7. ACS580-01, ACH580-01: Connect the brake resistor cable (if used) according to
the R1...R5 quick installation and start-up guide of the drive. Tighten the screws
to the torque given beside the figure.
8. Swing the main switch or terminal block stand platform back to its correct position
(8a) and tighten the screws to the torque given in the figure (8b).
9. +B056+F278, +B056+F316: Remove the fingerguard off from the main switch by
releasing the clip with a screwdriver (9a) and lifting the fingerguard off (9b).
10. Input cable II: Connect the input cable phase conductors as follows. Figure 10
shows a main switch but your drive can have a terminal block instead. Tighten the
screws to the torque given below figures 10 and 11.
+B056+F278, +B056+F316:
brown phase conductor to terminal 2T1 of the main switch
black phase conductor to terminal 4T2 of the main switch
gray phase conductor the terminal 6T3 of the main switch.