LG AR-DR12-05A Installation And Operation Manual page 151

Rooftop dedicated outdoor air system doas vx, base rooftop doas 800 to 5750 cfm, energy recovery wheel rooftop doas 900 to 9550 cfm
Hide thumbs Also See for AR-DR12-05A:
Table of Contents

Advertisement

Table 41: BACnet and MODBUS Points List, continued.
Variable
Binary Values – Read Only
Occupied
Unoccupied
Unoccupied Status
Unoccupied_Cooling_
Unoccupied Cooling Call
Call
Unoccupied_
Unoccupied Dehumidification
Dehumidification_Call
Unoccupied_Heating_
Unoccupied Heating Call
Call
Occupied Start Command
Occupied_Start
Unoccupied Start Command
Unoccupied_Start
Status to indicate startup is
Enable_Controls
complete and the unit is ready
General alarm point.
Optionally set to indicate
Global_Alarm
any alarm is active, or a
shutdown alarm is active
Shutdown alarm status. When
System_Shutdown_
true, System Enable will be
Alarm
set to false and the unit will
Indicates there is a open air
Damper_Open
path and the supply fan can
Indicates that the unit is
Cooling_is_On
Indicates that the unit is
Economizer_is_On
Indicates that the unit is
Heating_is_On
Dehumidification_
Indicates that the unit is
Mode_Enabled
Manual_Override_
Indicates that manual
Active
Cooling_Not_Locked_
Indicates that cooling is
Out
Heating_Not_Locked_
Indicates that heating is
Out
Preheat_Not_
Indicates that preheat is
Locked_Out
Indicates that the hot gas
HGRH_Purging
reheat value is purging
Description
Active Text
Occupied Status
Occupied Unoccupied
Unoccupied Occupied
On
Status
On
Call Status
On
Status
Start
Status
Start
Status
Yes
Alarm
Alarm
remain off
Open
run
Yes
cooling
Yes
economizing
Yes
heating
Yes
dehumidifying
Active
overrides are active
Allowed
allowed
Allowed
allowed
Allowed
allowed
Yes
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
BACnet and MODBUS Points
BACnet
Inactive
Object
Object
Text
Instance
Type
16
BV
17
BV
Off
18
BV
Off
19
BV
Off
20
BV
Stop
21
BV
Stop
22
BV
No
23
BV
Normal
24
BV
Normal
25
BV
Closed
26
BV
No
27
BV
No
28
BV
No
29
BV
No
31
BV
Inactive
32
BV
Locked Out
33
BV
Locked Out
34
BV
Locked Out
36
BV
No
37
BV
CONTROLLER
MODBUS
Register
Access
Hyst Index
Type
ReadCOV_
0
10002 Discrete
NoWrite
ReadCOV_
0
10003 Discrete
NoWrite
ReadCOV_
0
10004 Discrete
NoWrite
ReadCOV_
0
10005 Discrete
NoWrite
ReadCOV_
0
10006 Discrete
NoWrite
ReadCOV_
0
10007 Discrete
NoWrite
ReadCOV_
0
10008 Discrete
NoWrite
ReadCOV_
0
10009 Discrete
NoWrite
ReadCOV_
0
10010 Discrete
NoWrite
ReadCOV_
0
10011 Discrete
NoWrite
ReadCOV_
0
10012 Discrete
NoWrite
ReadCOV_
0
10013 Discrete
NoWrite
ReadCOV_
0
10014 Discrete
NoWrite
ReadCOV_
0
10015 Discrete
NoWrite
ReadCOV_
0
10017 Discrete
NoWrite
ReadCOV_
0
10018 Discrete
NoWrite
ReadCOV_
0
10019 Discrete
NoWrite
ReadCOV_
0
10020 Discrete
NoWrite
ReadCOV_
0
10022 Discrete
NoWrite
ReadCOV_
0
10023 Discrete
NoWrite
Size
151