LG AR-DR12-05A Installation And Operation Manual page 126

Rooftop dedicated outdoor air system doas vx, base rooftop doas 800 to 5750 cfm, energy recovery wheel rooftop doas 900 to 9550 cfm
Hide thumbs Also See for AR-DR12-05A:
Table of Contents

Advertisement

CONTROLLER
Sequences of Operation
Water Source Heat Pump, continued.
Entering Water Temperature Alarms: The following alarms occur based on coaxial coil entering water temperatures:
• An entering water temperature alarm activates:
• When cooling and entering water temperature is greater than set-point; or
• When heating and entering water temperature is less than set-point.
• The controller responds to an entering water temperature alarm:
• When heating, it displays a low entering water temp alarm.
• When cooling, it displays a high entering water temp alarm.
• An entering water temp alarm automatically resets:
• When cooling and entering water temperature is less than set-point; or
• When heating and entering water temperature is greater than set-point.
Coax Coil Defrost, Heating: In heating mode, a water source heat pump may need to initiate a defrost cycle of the water coil to prevent a
complete freeze.
1. Initialized: The saturated suction temperature determines when a defrost cycle occurs. The following conditions must be true:
• Saturated suction temperature is less than the fluid freeze temperature set-point; and
• Cold weather start is not active; and
• The unit has controls enabled.
2. Termination: The defrost cycle terminates when the active circuit's saturated suction temperature is greater than the cancel set-point. At
defrost cycle termination, the unit reverts back to heating mode operation.
3. Water Source Heat Pump Heating Lockout: Water source heat pump heating mode is unavailable when:
• The water source heat pump defrost cycle continues for more than the maximum defrost time; or
• A defrost cycle is initiated three times in any one-hour period.
• Each strike created by a defrost mode entry clears one hour after the strike occurs.
4. Water Source Heat Pump Heating Lockout Reset: The water source heat pump heating lockout resets when:
• The water source heat pump heating lockout occurred more than two (2) hours prior; and
• The saturated suction temperature is greater than or equal to the cancel set-point; or
• If the maximum defrost time triggered the lockout, the outside air temperature is greater than the fluid freeze temp set-point plus 10°F.
Supply Fan Modulation: In heating mode, if the supply air temperature is less than 60°F, the supply fan speed decreases to maintain 60°F.
126