6.6 Examples

6.6
Examples
6.6.1

Example Acoustic channel 1

Acoustic channel 1 (1/So1) should:
● Work with normal measuring sensitivity.
● Trigger a measured value alarm in the event of a sensor fault.
● A pre-alarm from measured value 20 dB.
● A master alarm from measured value 40 dB.
● Alarm after value exceeded for 60 s.
● Save alarm.
● Not report pre-alarm.
● Report main alarm with digital output 1.
Procedure
1. Connect the acoustic emission sensor, as described in the "Connecting acoustic emission
sensors" section.
2. Press the <PAR> button for five seconds to switch to the parameter menu.
3. Using the
4. Using the
5. Using the
6. Using the
20 dB.
7. Using the
8. Using the
40 dB.
9. Using the
10. Using the
seconds.
11. Using the
12. Using the
13. Using the
14. Using the
15. Using the
16. Using the
with digital output 1.
50
and
buttons, set parameter "P. 1".
and
buttons, set the parameter value "on H".
and
buttons, set parameter "P. 5".
and
buttons, set the parameter value "20". A pre-alarm is triggered from
and
buttons, set parameter "P. 6".
and
buttons, set the parameter value "40". A main alarm is triggered from
and
buttons, set parameter "P. 13".
and
buttons, set the parameter value "60". The alarm is triggered after 60
and
buttons, set parameter "P. 14".
and
buttons, set the parameter value "St.Ac". Alarms are saved.
and
buttons, set parameter "P. 15".
and
buttons, set the parameter value "oFF". Pre-alarms are not reported.
and
buttons, set parameter "P. 16".
and
buttons, set the parameter value "doAL1". Main alarms are reported
SITRANS DA400 for oscillating positive displacement pumps with protection against explosion