ABB PSTX Series Installation And Commissioning Manual page 57

Hide thumbs Also See for PSTX Series:
Table of Contents

Advertisement

6.2
Local control from keypad
WARNING
When you change from local control to remote
control, the setting applies immediately. If the
remote setting has direct motor start it can start
the motor automatically and can cause personal
injury.
WARNING
After a power loss, software upgrade or cycling of
the PSTX Control supply, the PSTX automatically
is set in remote control. Remote control is the
default control of the PSTX.
INFORMATION
Keypad control has the highest priority and
overrides all othe control methods
This chapter gives a description of how the local control
interface works. Use the local control to start and
stop the motor from the keypad. When local control is
selected, you can only control the Softstarter with the
keypad.
Table 3
Local control from keypad
Function
Start/stop
R\L
Motor Jog *
* For information about Motor jog see
To go to the Motor Jog, follow this path in menu:
Menu
Motor jog
6.2.1
Start key
The start key is the start switch for the Softstarter. Push
this key to start the motor and operate with the set
1
parameters. See
in Figure 6.15.
6.2.2
Stop key
The stop key is the stop switch for the Softstarter.
Push this key to stop the motor with the set parameters.
You can push stop command during the start ramp if
2
necessary. See
in Figure 6.15.
6.2.3
R\L-key
R\L-key stands for Remote or local control.
Use this key to control the Softstarter remote from digital
input, fieldbus or local from the HMI.
3
See
in Figure 6.15.
Description
Start and stop the motor with the
keypad.
Change between local and remote
control
Run the motor as long as Jog is
pushed.
chapter
6.2.4 Motor jog.
1SFC132081M0201
| Installation and commissioning manual | Human machine interface (HMI)
WARNING
When changing from remote control to local
control, the softstarter stays in present state. That
means, if the the softstarter is running the motor
when switching between the remote control and
local control, the softstarter will continue to run
the motor.
WARNING
Since the keypad has highest priority, when in
local control, neither the digital inputs nor the
fieldbus communication can stop the motor if it
is running. When in local control the only stop
command that can stop the motor is the stop key
on the keypad.
Options
Options
L
N
100-250V
50/60 Hz
K4
K4
K4
Start Stop Reset In1 In2 DGND DND +24V GND
PSTX
3
3
2
2
Figure 6.15
Local control
Menu
Menu
1
1
4
4
4
Stop
Start
1
1
6
57